Laserfiche WebLink
� <br /> . i.� ': <br /> � � . <br /> E '�• <br /> � i � CITY OF EVERETT <br /> � . . . <br /> I � ' SUILDING DEPARTMENT �1 <br /> PLAN CORRECTION SHEE7' <br /> DATE June 7, 1984 " USE MeEical Offices <br /> OWNER Norton Building PartnQrship USE ZONING R-3 <br /> CONTRACTOR M. R. Hansen Company FIRE ZONE _ <br /> ARCHITECT Steve Storaasll Company OCCUPANCY GR�UP 8-2 -�+ <br /> ... <br /> JOB SI'iE ADDRESS 3216 Norton Avenue OCCUPANT LOAD 112 m <br /> TYPB r�F CONSTRUCTION V-N PLAN CHECK N0. 84/13183 <br /> � M Y�1 <br /> "'1 � <br /> In response to your application for a permit, your plans and specifications �_ <br /> have been examined and you are advised that the issuance of a permit is o m <br /> withheld for the reasons hereinafter set forth. NOTE CAREFULLY: Answer m� <br /> questions and make explanations bX co_�r_rectin_g�ori inal plans , and new .� c <br /> plans must be submitted to the Bui�ing �nspection e�t. (This sheet � � <br /> must be returned with original plans and specifications or they will be �-'x,� <br /> filed as new business. ) „ <br /> .o z <br /> c <br /> Item No. UNIFORM BUILDING CODE 1979 EDITION CODE SEC. � _ <br /> .. .. <br /> K N <br /> � O � <br /> ,� Subnit details of end connections of 3-1/8" x 28-1/2" " <br /> glulam roof beams. = m <br /> . . �t .. <br /> 2 J Submit one copy of structural calculations. o � <br /> r' (� rl <br /> 3� Masonry veneer supported on wood roof framing (See 17/A-5) Sec. 2516 = � <br /> _` � is questionable. .i� <br /> ) m <br /> ..- �g,l Face nailing of framing requires 16d not Bd. (See Detail Table 25-P � <br /> 11/A-4). _ <br /> a <br /> . _ <br /> 5. Attic ventilation requires 17 roof ventilators as detailed Sec. 3205(c) -� <br /> on 3/A-7 but only 10 are provided. N <br /> 6. Submit one copy of heat loss calculations to verify building � <br /> conforms to 5tate i.nergy Code. � <br /> m <br /> 7. Provide draft stops in attic. Sec. 3205(b) <br /> 8. Provide draft stops in floor construction. Sec. 2517(f)2 <br /> 9. No ventilation is provided in roof. over Elevator Equipment Sec. 3205(c) <br /> and Electric Room or roof over Waiting 202. <br /> 10. Provide continuous vap�r barrier on warm side of all State Ener y Code <br /> insulation in roofs and exterior wa11s. 601�f) ` <br /> 11 . Exit doors to conform with Sect•ion 3303(c). <br /> I age 1 of 2 <br /> , <br /> � � <br />