Laserfiche WebLink
CI'fY OP F.VF.RF:TT <br /> BUILDING DF.YARTMENT <br /> PLAN CORR�CTION SHEIi'P <br /> DA7'E March 27, 1984 USE <br /> 014NER Charles Spoelstra USIi ZO�ING <br /> CONTRACTOR PIRIi ZONE <br /> ARCHITECT _ OCCUPANCY GROUP <br /> JOB SITE ADDRLSS 2923 Oakes OCCUPANT LOAD <br /> TYPE OF CONSTRUCTION PLAN CHECK N0. 84/13147 <br /> In response to your application for a permit, your plans and specifications <br /> have been examined and you are advised that the issuance of a permit is <br /> withheld for the reasons hereinafter set forth. NOTIi CARGFULLY : Answer <br /> questions and ma?;e explanations b�correcting origi.nal plans , and new <br /> plans must Ue submitted to the Buil�cing Inspection Departm�nt . (This sheet <br /> must be returned lvith original Plans and specifications or they iaill be <br /> filed as new business . ) <br /> Item No. UNIFORht BUILDING CODE ] 979 EGI'PION CODE SEC. <br /> 1 • Proposed 4" ;c 14" beam is overstressed. <br /> Z. Dimensions on cross-section drawings are different than � <br /> shown on floor plan. � <br /> � <br /> 3. New load on existing brick pier may cause soil bearing � <br /> pressure to exceed allowable. <br /> 4 . An inspection of the building on March 27 , 1984 revealed <br /> rot has caused the rear stair to be removed and also made H ,- <br /> the porch and roof unsafe. Additional areas are suspected y "' <br /> of being in substandard condition such as the mudsill � '_ <br /> � � <br /> supporting the floor joists and soufh wall . No permit <br /> for construction will be issued without receipt of a written � � <br /> report by a licensed architect or st�uctural engineer � <br /> regarding the condition and integrity of the b ' ing. � F <br /> � � � <br /> � � <br /> ' � ; <br /> Ja k E. frets � c <br /> /P ans Examin r � o`. <br /> � ~ <br /> � �� C��� S�'O«c.Ce--��, ..���?��`( , , . <br /> ���� <br /> � �. <br /> �, <br /> r <br /> � : <br /> Pagc 1 of 1 � <br /> � <br /> � <br />