Laserfiche WebLink
October lb� 19G6 <br /> Parkland Electric RE: 6G04 UlympEc Drive <br /> 13415 Pacific Ave �verett� Nashington <br /> Tacoma� Washinpfon <br /> uen:ler,en: <br /> The following corrections must be r�de ai 66J4 Olympic Drive: <br /> 1. Service racPw:�y not proper size for wnductors used� 7ables : <br /> and 5� National Ele�trical Code. <br /> 2. Ground wire must terminate on water pipe - Section 250-112(�) <br /> Nationa7. Electrical Code - the use of ground rods in lieu of the ccid <br /> water line is not recognized within the City. Connection must be <br /> accessible. <br /> 3. All wiring under ihe M�use is rejecieo - violation of Sections <br /> 336-5�6�a) and 6� IVati�nal Electric�l Code. <br /> 4. All hc�ters end boxr:s arc in violntion to Section 250-114(n) <br /> Na{ionA1 Electricel Coue on gr�undi���, <br /> 5. Grounding wires are not properl} spliced on any of tl�,e <br /> conneciions within the boxes or heaters - Section 110-17� PJatioi;:i <br /> Electrical Code. <br /> 6. Too much insuletion he= been rerxvec fren the wir� tAt ihe tcrniinal= <br /> on the thernasteis� leoving bare wire in :ontac{ with the melal pir{c <br /> on the boxes - Seciion 11'J-20� National Electrical Codv. <br /> 7. Plastic boxes are not allowed in the City of Everetc - Se:ticr <br /> 6--17� Ci{y Ordinance 9I�118. <br /> b. Nbre than one cr.bie cannot be terminated in a single r.:,nnecto� - <br /> Section 370-7 of the Na{ional Electrical Code. <br /> 9. Branch circuite on the heat circuits exceed the allowable lo�d on <br /> the circuit - Section 210-23�6)� National Electrical Code. <br />� • <br />