- _ � �-, <br /> PC k49450 <br /> October 25, 1995 <br /> Page 3 <br /> �2. An 8'-6� floor to floor height is indicated for the basement parldng ga�age. Please <br /> provide clear, detailed drawings to ensure 7'-0" minimum headroom within garage. <br /> Include sprinkler piping, heads and hangers, waste piping, beams and any other <br /> potential obstructions. (During conswction will not be the time to discover a problem. <br /> As we have had a great deal of trouble on past projects with this requirement we will <br /> not be very understanding). Sec. 311.2.3.3. <br /> � 13. A 17" min. deep knee space is required at accessible sinks. Sec. 1106.11.7.3.1 Re: <br /> Defail 2 sheet A 13. <br /> ,/14. Please provide enlarged stair plans for all levels of each stair. IDustratc handrails, <br /> eztensions, signage, etc. <br /> ✓15. Please call out wall rype on floor plans. <br /> �16. Most of the units have a 4' deep foyer. 60" min. is required by Sec. 1106.10.3. <br /> ✓17. Please provide detailed dimensions for walls within units. <br /> �� <br /> �(/� 18. Please indicate exhaust fans (including cfm rating) and outdoor air inlet system per <br /> VIAQ Code. Please also indicate and detail any shafts that may be required for these <br /> systems. <br /> ✓19. Please review the attached combustible piping policy sheet. <br /> ✓20. Units C & O bathroom doors must provide a 32^ min. clear opening. <br /> ✓21. May units have re-lites to the main corridor (E & F for ezample). The area of these <br /> re-lites cannot ezceed 25% of the uea of the common unidcorridor wall. Sec. <br /> 1005.8.2. <br /> ✓ 22. Many of the enlazged pians are not oriented the same as the iypical floor plan. Please <br /> revise. (See also item 10). <br /> � 23. The eating bar in ani�K nust be accessible per Sec. 1106.19. <br /> i/24. Please detail (or specify) any door thresholds (s��ecifically deck doors) that are required <br /> to be acce�sible. <br />