device must be provided for the landscapi.ng �,::r Section <br /> 35.130 B of the 2oning Code. <br /> 18. Hased upon 19,800 square feet of type II-N �or;;�truction <br /> sprinklered constr��ction, the minimum fire flaw requireme-t (E <br /> 1,500 GPM. <br /> 19• One fire hydrant must be installed, with location *.o Ge ��uroved <br /> by the Fire Marshal. <br /> 20. A sprinkler syetem complyinq with UBC standard 78-1 and/or NFPA <br /> atandard 13 must be provided. Plans !or the syatem must be <br /> submitted to the Bnildinq and/or Fire Departmenta fcr <br /> examination end approval. Plans must include deteila !or the <br /> underqround water mains that vill aupply the system. <br /> 21• Abo�e-qround sprinkler pipinq must be hydrostatically tested as <br /> established in NFPA standard 1�. Underqround Fipinq mue� <br /> hydrostatically tested and lluahed as astablietied in NFp� <br /> standerd 24 for private fire mains. All nuch tests must be <br /> witnees�d by a Fire Depnrtment inapector. Planse call 259-8710 <br /> to meke an appointment for inspaction. <br /> 22. Contractors materials and test certificetae must be submitted to <br /> the Everett Fire Department prior to isauancs of any Certificate <br /> of occupancy. Please call 259-8726 tor more infozaation. <br /> z3. certain additional fire protection meesures msy be neceasary, <br /> dependinq on whether a portion o! the builinq is us�d for <br /> hi4h-piled storaqe, if qreater than 2,500 aquar� feet of lloor <br /> az•ea is used for hiqh-piled atoraqe, a permit will be required <br /> fr�m the Fire Department. a floor plan muet ba submitt�d with <br /> hi9hipiled�storaqeu areasg pe�it� ehowinq tha location of any <br /> informat' •�, Please call (206) 259-g7Z6 for more <br /> za. The corz•ecr nddress must be clearly posted upon eech buildinq in <br /> such a mani.ar as to be visibls end leqibl• from th� str�et or <br /> uomust b� cleerly poated on a p�nean�nt siqn at tGe stre�t entry <br /> thc �_�plex. Suite or buildinq nuubers must elso ba pcsted <br /> Po� �•..ch bv lding. <br /> 25• 1► portabls fire extinquisher with e minimua UL ratinq o2 2A mueL <br /> be �rovidel within 75 fee`, trav�l distenc� of all portions of <br /> each bctildinq on each floor durinq construction and prior to <br /> occupancy. Port.:ble fire protection must b� provided throuqhout <br /> priorutodisaunnce eof the Cer i!1 et� ot ocaypQ��yiforn Fir� Code <br /> 26. All required ecceas roadri and tira hydrants must be in service <br /> pricr to commencement of constructinn. <br /> 6 <br />