Laserfiche WebLink
Fire Protection Plnn <br /> Eaqle Herdwere i Gnrden, Everett <br /> Pnqe 3 of 9 <br /> This hiqh density system is inetnlled for tvo reasons. The <br /> firet is to provide aa overdesiqn for t«e Class IV commodity <br /> thnt mny be stored up to twenty ieet. The se:cond is to provide <br /> protection for the epproximately 25 class V coumadities. (See <br /> class V section on paqe five) . <br /> FL•06 SPACS3 - RACI� STORASB <br /> Lonqitudinel flue epeces will be �raiatained in the bnck of all <br /> double row rncks. Tha width of racks will not exceed 48 inclxes. <br /> � 48" Mnximum <br /> Width <br /> Double Row Racks <br /> Lonqitudinel <br /> (6nd view) Flue spece <br /> Transverse flue spaces are required on ell double row recks <br /> reqardless of the type ehelves used. <br /> Traneverse Flue Spaces <br /> Double RoN <br /> Racka <br /> (Front View) <br /> AI9L8 <br /> it ie imFwrtnnt thnt the above requiremente are followed to <br /> allow for proper eprinkler penetration. <br />