Laserfiche WebLink
� �vBcic wo�urs <br /> ; <br /> , <br /> � <br /> � <br /> , <br /> ; <br /> i ltarch 6, 1992 <br /> ! <br /> i <br /> ; Botes�h, Nash 6 Hall <br /> S 4206 Hoyt Avenue <br /> � Everett, Washington 98203 <br /> ; ATTN: Jeff Moore <br /> s <br /> � SUBJECT: 916 PACIFIC AVENUE (PROVIDCNCE HOSPITAL) <br /> j BACK-FIAW PRE\IENTION <br /> 7 <br /> i <br /> e <br /> Dear Jeff: <br /> � During the Water Department's review of the existing fire service for the <br /> hoapital, it vas discovered that this service has a single check-value <br /> � • rather than the required double-check valva assemble as shown on the C-1 <br /> plan for tha hoepital expanaion. The City would like to require that <br /> ; this service be upgraded to meet existing standards in con�unction vith <br /> ' pending expaneion af the hospital. <br /> i <br /> � I am enlinting the services of Don Wahl in the Water Department to <br /> provida an estinata of coat for the Water Department to do this vork. A <br /> � copy of tha eetimate aill be sent to you for discussion when it is <br /> I completed. <br /> We suggeat you discusa this change with your sprinkler system <br /> ! designer/inataller. The extra check-valve may provide a lose of flow <br /> 1 that should be conaidered in the syatem design. <br /> � <br /> iIf you have any questions please contact our office at 259-880 . <br /> � Sincerely, <br /> 1 <br /> i <br /> i � r Cr ford <br /> . pssYsta Public Works Director <br /> � <br /> i <br /> � Rl;LC:e{l�1e1469.2� <br /> � cc: Dan Mathias <br /> Bill Bruce <br /> ( <br /> CITY OF EVERETT• 3200 Cedar Street• Everett, WA 98201• (206) 259-8800• Fax(206) 259•8882 w <br />