Laserfiche WebLink
FIItE AND LQ►E SAFBTY lROGRAM MANACER'S BEVISW CObQNSNT3 <br /> b�PADDOCIC <br /> Ptaoe: (360)705�6784 <br /> FAX: (360)705-6654 <br /> NET: I1�@'0303 �hub.do6.w�.`ov <br /> FACIUTY: Provideoce Cieaeral Medica!Centa <br /> Pit0,1ECT: Be6tviorat Health Rebcation <br /> CRS�: 97-OOS8-4962-002 <br /> DATE: August 25, 1997 <br /> 1. pieaae verify that dooc openit�s 128 and 131 will be provided with smoke gacicets. <br /> Sec. 1005.8.1,Unifwm Building Code <br /> 2. T6e laundry alcove(l l2)is reqwred w be separated fiom the cocridor by+t Iwt ooe <br /> dour conawction. The door openin`is required to be protected by at leut a ZO-minute <br /> smolce and draft control assembly. Sec. I005.1; I005.7: I005.8.1, Unifam Building <br /> Code <br /> 3. Completc plans and specificuions for the fire alarm system insnllation or <br /> modification are required W be aubmitted fa�eview and approval prior to system <br /> installadon. Plans and specifications arc required to include,but not be limited to,a floa <br /> plan;location of all alarm-ini6ating and dartn-signaling devices;alartn-control and <br /> tmable-signaling equipment;annunciation;power connectioa;b�ttery cakulalions; <br /> conductor type and sius; voltage drop calculations;name,addresa,and pl►ooe number of <br /> the company receiving off-ptemises tronsmission of alum; and mmufactwer,nadel <br /> numbers and listing infomiation for all equipment,devices and materials. Sec. 100L3, <br /> Uniform Fia Code <br /> 4. Firc sprinkler system working plaea shall be submitud for apptuval befae my <br /> equipment is installed a temodeled. Deviation from the approved.plans will requiie <br /> pemvssion. Waking plans shall include dl items at noted in Sectioe 6-1.L1, Unifotm <br /> Building Code Standard 9-l. Sec. 6-1, Unifotm Building Code Standud 9-1 <br /> #4�Rf►R NOT APPROVED •••"• <br />