Sister CarAelina, Administrator <br />Providence Hospital <br />April 6, 1959 <br />Page 2 <br />9. the holes noted around the pipes in the X-ray room must be filled <br />with plaster. <br />10. All obstructions, such as chatra, stands, wheel chairs, etc., east <br />be removed fro^ all hallways and exits and these areas maintained free of cuch <br />obstructions in the future. <br />11. All flrmmeble materiel must be removed from fire exits. <br />12. All ioory on the dumh-waiter shaft frocr the pharmacy aunt he approved <br />fire ^core which may be held open only by the use of 6hsible links. <br />13. All ioors on the leun.,ry chute Tact be mede one hour fire reetetent., <br />metal lined, and m,ay be held open only by the use of fusible links. <br />14. Install a deflector in the diet kitchen window which will prcvont, <br />the wind from blowing out, the flrme on the gas burner. <br />15. The veneer wells InF.talled in the short weet wing off the lobby <br />must hF covered with 5/8 inch plasterboard. (Third floor) <br />16. All oxygen tanks must be either mounted on approved carts or chained <br />to the bed then in use in patient rooms. <br />17. Repair the fire door on the exit from the maternity room ao that it <br />1!111 close tightly. <br />18. Alcohol in the pharmacy ,:vat be kept only in metal containers of not <br />more than 1 gallon capacity. <br />19. All grain alcohol over one gallon must be stored in an approved room <br />of nne hour fire realatant material, constructed for that purpose, preferably outside <br />of the building, with vents at top and bottom and with vapor -proof light end switch. <br />20. Alcohol amst not be draim from a drum by Errvity but only by nn <br />approved pump. <br />21. The portable electric heater must be removed from the patholo€y and <br />hioo_1 r1onors' rest rooms. <br />22. Install an rp,roved electric outlet for the coffee urn in the staff <br />lounge. <br />23. An approved room or manifold enclosure, constructed ne described in <br />paragraph 7 above, must be provided for the storr_l;e of oxidizing rases (nitrous oxide <br />and oxygen). If the storage of oxygen or nitrous oxide is in excess of 1500 cu. ft. <br />mEmifold (or cylinder) capacity, the room must be vented to the outside. Provide <br />reeks or featentngs to protect cylW ers from accidental damage or dislocation. <br />2/„ Femove all storage from the elevator control room in the basement. <br />