Laserfiche WebLink
� <br /> Carl A. Munding <br /> Providence Hospital <br /> CCRS #�87820-1211-001 <br /> November 13, 1987 <br /> Page Two <br /> 4. Please verify ETO alarms and evacuation systems. NAC <br /> 248-18-680(3)(b) (iv). <br /> MECNANICAL CONSULTANT'S REYIEW <br /> Claude V. Laws, P.E. 753-3489 <br /> Mechanical Items: <br /> 1. What is the purpose of the hood in pack area M57 <br /> 2. Are the hoods in IV room N5b recircutating type7 If not, show <br /> duct connections to the outside, make-up air, etc. <br /> • 3. Verify locations of required fire-rated wa11s and ceilings with <br /> architect and show all ffre dampers. <br /> 4. Label and connect ceiting diffuser to ducbvork in respiratory <br /> therapy M9. <br /> 5. There appears to be an extra ceiling diffuser in office N26. <br /> Eitfier label and conn�!ct it to ducA+ork or delete it. <br /> 6. Verify requirements of ethylene oxide system. A1arm system wt11 <br /> be required. Transfer grille to preparatton and packing N11 mqy <br /> not be a1la+ed. Gas bottles may not be atlowed to be stored in <br /> laation sharn. <br /> 7. Specify temperature controls and shoMr thermostats. <br /> �' B. N111 a fire sprinkter system be specified? <br /> 1 Etectrical Items: <br /> i <br /> 1. Complete all schedules. <br /> 2. If ar�y 1igh4 fixtures are recessed in rated ceilings, they must be <br /> tented. Yerify construction with architect. <br /> 3. Shav locations of a11 requi��ed alarms. <br /> 4. Specffy or show fire alarm system on drawings. <br /> 5. Ne electrical outlets are shown in rooms �"4, 5, 48, 63, and wait- <br /> in�� area. Verify that none are required. <br /> 6. Verif� that telephone outtets will not be needed in rooms N14, 18, <br /> 23, 38, 48, 56, and 68. <br />