2009 N.',�shington State E^^�gy Code Compliance Form for Nonresidential ��d Multifamily Residential
<br /> ' • � • . • .
<br /> 2009 Washington Slate Energy Code Compliance Forms lor Nonresiden4al ana Mulhlamily ftesidenUal
<br /> Rensed November2010
<br /> I'rescriptive Spaces Occupancy: Q Warehouse or Parking Garage QQ Other
<br /> Lightin9
<br /> Qualification Checklist � Check if 95%or more of G■Wres complV with 1.2 or 3 and rest are ballaste .
<br /> No;e It octu anc � e is"Other"and lidure FixWreS:
<br /> p y yp 7. Fluorescent fiawres with a) 1 or 2 Iwo lamps,b)reflector or louvers,
<br /> ,nswer is checketl.ihe num�er ol fzWres in•($ecti0fl c)5-60 watt T-1,T-2,T-4,T-5,T-8,or CFL lamps,and d)hard-wired eleeimnic
<br /> n,e space i,nct i�miied by Cotle. Geariy �5z�1 dimming ballasts. Serew-in CFL LxWres and traeking lighling do nol qualify.
<br /> mtl�cate these spaces on plans. I(noi
<br /> quahGed,do LPA Calculalions 2. Melal Halide with a)refiector b)ceramic MH lamps<=150w c)electronic ballasts
<br /> 3.LED lighls.
<br /> TABLE 15-'1 Unit Li htin Power Allowance LPA LPA WIft
<br /> Usc LPA Wlft Use
<br /> Aulomotive faciliry 0.85 Otfce b�ildings,officeladminisUative areas in facilities 0.97
<br /> of olher u_^.types(including bul not limited to schools,
<br /> hos itals,in:litulions,museums,banks,churches' 020
<br /> Convention center 1.10 Parkin ara ��s
<br /> Courthouse 1.10 Penitentia ano olher Grou I-3 Occu ansies 0.90
<br /> Cafeterias,fast food establishmeNs� 120 Police and fire stat�c^s
<br /> reslauranis/bars' 1.00
<br /> Dormita 0.85 Post oN,ice
<br /> Dvreling Units 1.00 Retail ,retail banking,m�'I concourses,wholesale 1.33
<br /> slores allet rack shelvin
<br /> Exercise center 0.95 School bui�dings(Group E Occupancy only),school 1�4�
<br /> class�ooms,da care centers
<br /> 0.95 Thealer,molion icture 0�97
<br /> G mnasia,assemblv s aces �25
<br /> Heallh care clinic 1.00 Thealer, erfortnin arts 0.80
<br /> Hospital, nursing homes,and olher Group I-1 and 1.20 TranspoAation
<br /> I-2 Occu ancies 0.50
<br /> Holel/motel 1.00 Warehuuses � 20
<br /> Laboralory spaces(all spaces nol classified 1.62 Workshops
<br /> 'laboratary"shall meet office and other appropriate
<br /> cate ories
<br /> Laundries 1'20
<br /> Libraries 1.20 Plans Submitted tor Common Areas OnI
<br /> ManuFaclurin facilit '.20 Main floor buildin lobbies ezce t mall concourses 0.80
<br /> Museum 1.00 Common areas,corridors,toitel facilities and
<br /> washrooms,elevator lobbies
<br /> Footnotes(or Table 15-1
<br /> 1) In cases in which a general use and a specific use are lisled,lhe specifc use shall apply.In cases in which a use is not mentioned
<br /> specifically,the Unit Power Allowance shall be determined by the building official.This determination shall be based upon ihe most
<br /> comparable use specifed in the lable.See Section 7512 for exempt areas.
<br /> 2) The watts per square fool may be ircreased,by 2%a per foot of ceiling heighl a6ove 20 feet,unless specificalry direded othenvise by
<br /> subsequent foolnotes.
<br /> 3) Watts per square toot of wom may be increased by 2%per foot of ceiling height above 12 feel.
<br /> 4) For all other spaces,such as seating and common areas,use lhe Unil Light Power Allowance for assembly.
<br /> �) Walls per square foot of room may be increased by 2'/o per foot of ceiling height above 9 feet.
<br /> 6) Reserved. '
<br /> 7� For conference rooms and oKces�ess than 150ft' with full hc�ght paifitions,a Unit Lighting Power Allowance ot 1.7 wlft'may be used.
<br /> B) Reserved.
<br /> 91 For indoor spod toumament couAs with adjacent speclator seating over 5,000,lhe Unit Lighling Po�verAllo�vance for the court area is
<br /> 2b0 W!%�.
<br /> �� uisplay window ilWrnination inslalled within 2 feet of the window,provided that the display wirdow is separated from the retail space by
<br /> ! c:alls or at least'.hrae-quarter-height partitions prensparenl or opaque)and lighting for free-slanding display where the lighting moves
<br /> c.dh the display are ezempt.
<br /> An additional lig;�ting power allowance is allowed for merchandise display luminaires installed in retail sales areas that are specifically
<br /> I �.�esigned and direcled lo highlight merchandise. The following additional watlages apply.
<br /> i, i.0.6 watts per square foot of sales tloor area aot listed in items ii and iii below;
<br /> ii. 1.4 watts per square fool of furniWre,cbthing,cosmelics or aAwork floor area;or
<br /> � iii.2.5 watts per square foot of jewelry,crystal or china floor area.
<br /> The specified Iloor area for items i,ii,or iii above,and the adjoining circulalion palhs shall be identified and specified on building plans.
<br /> Calculate Ihe additional power allowance by mWtiplying the above LPDs by lhe sales floor area for each departmenl excluding major
<br /> circulalion pall:s. The total addilional lighting power allowance is Ihe sum of allowances for sales calegories I,ii,or iii plus an additional
<br /> 7,000 watts for each separale tenant larger than 250 square feet in area.
<br /> The additional watlag=is allowed only if the memhandise display luminaires comply with all of the tollowing:
<br /> (a)Located on ceiling�mounted track or direclly on or recessed inlo the ceiling itself(not on lhe walq.
<br /> (b)Adjuslable in both the horizontal and vedical axes(vertical axis only is acceptable for tluorescent and olher fxtures with hvo
<br /> points oi track altachmenl).
<br /> This additional lighling power is allowed only if Ihe lighling is actually installed and automalically conlrolled,separalely fmm ihe general
<br /> lighting,to be tumed oH during nonbusines5 hours. This additional power shall be used only for lhe specifed luminaires and shall not be
<br /> used for any olher purpose. �/
<br /> This additional lighling power is aliowed only if ihe lighting is aclually installed. yn
<br /> 11) Pwvided thal a Iloor plan,indiwling rack location and height,is submitted,the square foolage for a warehouse may be defned,for �-��
<br /> computing the interior Unit Lighting Power Allowance,as lhe floor area not covered by racks plus the vertical face area(access side only)