Laserfiche WebLink
; <br /> Meg Haley �� n�C�� -G�?�. <br /> From: Klaus Janssen <br /> Sent: Wednesday, August 01, 2007 1:44 PM <br /> To: Meg Haley <br /> Subject: RE: Sprinkler submittals processed <br /> Meg, <br /> I agree with the following caveat: no excessive wiring (e.g. computer cable bundles) or nonmetallic piping, for that would <br /> constitute combustible storage. <br /> Klaus <br /> From: D7c9 Haley <br /> Sent: Wednesday,August 01, 2007 12:18 <br /> To: Klauslanssen <br /> Ce: Bill Bruce;Tany Lee; Steve Miller <br /> Subject: Sprinkler submiltals processed <br /> Klaus, <br /> Jessie (our new Permit Technician) is ser�ding over the following suppression permits to your o�ce. Bill Bruce has <br /> reviewed the submittals to meet TSG standards for double-check detector and back flow assemblies, where applicable. <br /> One quick question from Steve and me,we think that a suspended ceiling with metal roof trusses in Type III-B construction <br /> meets the qualification of concealed space not requiring spri�kler protection, per NFPA-13 8.14.1.2.2, but wanted your <br /> opinion. Thanks, <br /> —Meg <br /> « OLE Object: Picture (Device Independent Bitmap) » <br /> Meg�;{a.l�ey <br /> �lantiy��ca-»tii,n�:r <br /> Ciry of Everett <br /> 3200 Cedar Slmet <br /> EveretL W1198201 <br /> Ph:A25-?57-BII73 <br /> Fax:425-257-8656 <br /> www,ev c re t twa.o rq Id c la u I L a s o x 71 D=376 <br /> 1 <br />