2009 Washington State F �rgy Code Compliance Fortn for Nonresidential i Mullifamily Residential
<br /> • � • • .
<br /> 20C9 Washin�tan State Energy Code Campliance Forms lor Nonresitlential and MulGlamily Resitlential Revisetl November 2010
<br /> Prescriptive Spaces occupancy: Q Warehouse or Parking Garage QQ other
<br /> Qualification Checklist Lighting � Check if 95%or more of fiMures comoiV wilh 1,2 or 3 and resl are ballasted.
<br /> Note:If oaupancy ype is"Othef anC fiMure Fizlures: �.Fluorescenl fixtures with a)1 or 2 lwo lamps,b)reflector or louvers,
<br /> answer is checked,the number o1 funures in (Sedion c)5-60 watt T-1,T-2,T-4,T-5,T•8,or CFL lamps,and d)hard-wired eleclronic
<br /> the space is not limited by COEe. CleaAy 1521)
<br /> indicate these spaces on plans. 11 not dimming ballasts. Screw-in CFL fixtures and trecking lighting do not quali(y.
<br /> quaiified,do LFn Caiaiations. 2.Metal Halide wilh a)refieclor b)cerzmic MH lamps<=150w c)eledronic ballasts
<br /> 3.LED lights.
<br /> TABLE 15-1 Unit Li htin Power Ailowance LPA
<br /> Use LPA W/k Use LPA W!R
<br /> Automotive taciliry 0.85 Office buildings,office/administrative areas in facilities G.91
<br /> of olher use types(including bul not limited to schools,
<br /> hos itals,institutions,museums,banks,churches s
<br /> Convention center 1.10 Parkin ara es 020
<br /> CouAhouse 1.10 Penitentia andotherGrou 130ccu ancies 0.90
<br /> Cafeterias,fast food establishments , 1.20 Police and fire stalions 0.90
<br /> restaurantsfbars' 1.00
<br /> Dortnito O.BS Postoffice
<br /> Dweling Units 1.00 Relail ,retail banking,mall wnco�rses,wholesale 7.33
<br /> stores ailet rack shelvin
<br /> Exercise cenler 0.95 School buildings(Group E Occupancy only),school 1.00
<br /> classrooms,da care centers
<br /> G mnasia,assembl s aces 0.95 Theater,motion idure 0.97
<br /> Health care clinic 7.00 Thaater, erformin arts 1.z5
<br /> Hospilal,nursing homes,and other Group I-7 and 7.20 Transportation 0.80
<br /> I-2 Occu ancies
<br /> Hotel/molel 1.00 Warehouses 0.50
<br /> Laboratory spaces(all spaces not classified 1.62 Workshops �•24
<br /> 'laboratory'shall meet office and olher appropnale
<br /> cate ories
<br /> Laundries ��ZD
<br /> Libraries 1.20 Plans Submitted for Common Areas Onl
<br /> Manufacturin facilit 1.20 Mainfloorbuildin lobbies exce tmallconcourses 1.10
<br /> Museum 7.00 Comman areas,corridors,toilet facilities and 0.80
<br /> washrooms,elevator Iobbies
<br /> Footnotes for Table 15•1
<br /> t) In cases in which a genera�use and a specific use are lisled,the specific use shali apply.In cases in which a use is not mentioned
<br /> specifically,the Und Power Allowance shall be determined by the 6uilding oRcial.This detertnination shall be based upon lhe mosl
<br /> comparable use specified in lhe lable.See Section 1512 tor exempt areas.
<br /> 2) The walts per square foot may be increased,by 2°h per foat of ceiling heighl above 20 feet,unless specifically direded olherwise by
<br /> subsequenl foolnotes.
<br /> 3) Wads per square fool of room may be increased by 2°h per font of ceiling height above 72 feet.
<br /> 4) For all other spaces,such as sealing and common areas,use the Unit Light Power Allowance for assembly.
<br /> 5) Watts per square foat of room may be increased by 2°h per toot of ceiling height above 9 feet.
<br /> 6) Reserved.
<br /> 7) For conference rooms and offices Iess than 150k� with full heighl paAitions,a Unit Lighting Power Allowance of 1.1 w1R'may be used.
<br /> 8) Reserved.
<br /> 9) For indoor sport toumamenl couAs wilh adjacenl spectator seating over 5,000,the Unit Lighting PowerAllawance for the court area is
<br /> 2.60 W/ft'.
<br /> 10) Display window illuminalion instalied wilhin 2 feet of the window,provided that the display window is separated from lhe retail space by
<br /> walls or al leasl Ihree-quarter•height pa�tilions(transpamnt or opaquc)and lighting for free-standing display where lhe lighling moves
<br /> with lhe display are exempl.
<br /> An addilional lighting power allowance is allowed for merchandise display luminaires installed in retail sales areas lhal are specifically
<br /> designed and direcled to highlight merchandise. The following additional waltages apply:
<br /> I.0.6 watts per square foot of sales floor area nol listed in ilems ii and iii below;
<br /> ii. 7.4 walts per square foot of turniture,clothing,casmetics or artwork tloor area;or
<br /> iii.2.5 watts per square fool of jeweiry,crystal ar china Iloor area.
<br /> The specified tloor area for ilems i,ii,or iii above,and lh=adjoining circulation palhs shall be ident�ed and specified on building plans.
<br /> Calculale the additional power allowance by mulliplying the above LPOs by the sales fioor area for each departnenl ezcluding major
<br /> circulation paths. The total addilional lighting power allowance is the sum of allowances for saies categories I,ii,or iii plus an addilional
<br /> 1,000 watts for each separate tenant larger than 250 square feet in area.
<br /> The additional wattage is allowed only if the merchandise display Iuminaires comply with all of lhe following:
<br /> (a)Localed on ceiling-mounted track or directly on or recessed into the ceiling itseH(not on the wall).
<br /> (b)Adjustable in both the horizontal and vertical axes(vertical axis only is acceplable far fluorescent and other fuAures wilh hvo
<br /> points af lrack attachment).
<br /> This addilional lighting power is allowed only if the lighting is aGually instailed and aulomaticaily contmlled,separately from the generel
<br /> lighting,to be turned off during nonbusiness hours. This additional power shall be used only for the specified luminaires and shall�ot be
<br /> used for any other purpose.
<br /> This additional lighting power is allowed only it the lighting is adually installed.
<br /> 11) Provided that a floor pian,indicating rack localion and heighl,is submitted,the square footage tor a warehouse may be defined,for
<br /> computing the inlerior Unit Lighting Power Allowance,as the floor area not covered by racks plus the vertical face area(access side only)
<br /> �f�1�n�nnLn TL�Anin1��r�ll����.�.�n�Ar�G�nA in Hn�.���n 7+��I:r�n r�.�F����ti�A���nr�n��.��.n���Ta A��rnln
<br />
|