Laserfiche WebLink
5. Saction 034Z0� DONCRfiTE FLOAT UNPI'S, nnder p�n�ap61.6. w6par�nph B, dd <br />d�e foIIowing: "Calculadons and dnwinga elull be aeabd by and prepurd und«� the <br />direcdon of a Prof�ssional Strncdual Bngineer licensed in q�e �e of R►a�tingoOn,++ <br />6. Socdon OSS00, MBTAL FABRICATIONS, Part 2: Add the following puagraph 2,11: <br />2.11 CLSATS <br />A. Qats sMall be Wilcox-(}itenden Figure No. 409, or equet, hot-dippod galvanizod <br />cast gny iron. <br />7. Section 15325, SPRIIQKL.ER SYSTSMS: <br />A. Acticle 1.5, paragraph C: Add subparagiaph C.1 as follows: <br />1. For the p�upose of preparing bids, assume the following wata supply <br />information at the point where the existing water lateral connects to the <br />watet main in the streeC <br />a. Stadc pressure of lOS psig. <br />b. Residual pre.esure of 85 psig with 1,200 gpm flowing. <br />B. Article 2.1: Delete paragraphs B.3 and B.6. <br />C. Article 2.5: Delete paragraphs C.2, C.3, E, and F. <br />D. Ar6cle 2.10, paragraph A: Reptace "AUTO SPKR & STANDPIPE" with "AU1'p <br />SPRINKLER." <br />E. Article 3.6, para�aph B: Remove and nplace with the following: <br />B. Gau Valves: Install fire-protection service valves, located to control sov�ces <br />of water snpply exctpt from fire departrnent connections. <br />F. Article 3.6: Delete paragraph C. <br />G. Article 3.9, paragraph A: Add subparagraph A.4 as follows: <br />"4. Provide "Knox Box" key enclosure mounted on exterior of dry pip� system <br />enclosure. Coordinate with Everett Fire Departtnent" <br />Addendum No. 2 <br />PAGE 2 OF 3 <br />