4 <br />rLx <br />ELEVATION <br />Q UL—FM LISTED SOFT SEATED STATE APPROVED DOUBLE CHECK DETECTOR VALVE ASSEMBLY WHICH MUST BE INSTALLED IN THE SAME ORIENTATION <br />FOR WHICH IT WAS APPROVED. ASSEMBLY TO INCLUDE; TEST COCKS. 3/4' BRASS OR COPPER BY PAS WITH IN LINE VALVE. AND A 5/T REMOTE <br />METER. METER TO BE READ IN CUBIC FEET AND BE REMOTED TO AN EXTERNAL WALL OF BUILDING METER BOX. <br />O UNIT —FLANGE WITH SET SCREWS OR MJ a FL ADAPTER WITH MEGALUG OR GALVANIZED SHACKLE TO MAIN WITH 2-3/A' RODS. OR MJ RETAINER <br />GLANDS FOR BOTH UPSTREAM AND DOWNSTREAM OF ASSEMBLY. <br />O3 DUCTILE IRON PIPE (SIZED AS REQUIRED) CLASS 52. <br />Q4 TWO GALVANIZED ADJUSTABLE PIPE SUPPORTS FOR 2 1/Y OMM AND LARGER PIPE. <br />QS A SUFFICIENTLY SIZED FLOOR DRAIN OR WALL FOOTING DRAIN MUST BE PROVIDED IN THE SAME ROOM. <br />© EXTERNAL DOOR WITH KEY IS REQUIRED. EITHER A LOCKSET IN THE DOOR HARDWARE OR A KEY VAULT (I.E. SUPRA S.S.) WITH A 1 5/S DIAMETER <br />X 1 1/6' LENGTH MORTISE CYLINDER. MOSTSE CYLINDER MUST ACCEPT THE CITY STANDARD 'BEST LOCKING SYSTEM. THE WIDTH AND HEIGHT <br />Or THE DOOR($) MUST EXCEED THE WIDTH AND HEIGHT OF THE ASSEMBLY. CLEARANCE BOTH INSIDE AND OUTSIDE ROOM MUST BE SUFFMIENT TO <br />REMOVE ASSEMBLY INTACT. THE ASSEMBLY MUST BE FULLY ACCESSIBLE (2rT IAN HORIZONT.'1 CLEARANCE TO ALL WALLS AND OR EGUPMENT) FOR <br />TESTING AND REPAIRS. <br />O FLUSHING CAPABILITIES MUST BE PROVIDED WITH A Y FLUSHING LINE DOWNSTREAM OF ASSEMBLY TO OUTSDD OR SUFFICIENTLY SIZED INTERNALi <br />DRAIN. <br />80 WHERE ASSEMBLY IS LOCATE ABOVE EXTERNAL GROUND LEVEL ALL BENDS REWIRED TO LOWER INLET PIPE TO PROVIDE REQUIRED EXTERNAL ■ <br />GROUND COVER SHALL BE FLANGE FITTINGS OR BE WITH HORIZONTAL AND VERTICAL THFIUST RESTRAINTS. <br />O9 THE ROOM SHOULD BE INSULATED WITH R-19 INSULATION OR GREATER AND HEATING TO ABOVE FREEZING. ONLY CONSTRUCTION MATERIALS THAT <br />CAN WITHSTAND OCCASIONAL SUBMERGENC, WILL BE ALLOWED. <br />GENERAL NOTES <br />1. TEE GTE VALVE REQUIRED ON AWN. <br />2. SINGLELE DETECTOR CHECKS <br />ARE NOT APPROVED BACKFLOW PREVENTION DEVICES. <br />3. ASSEMBLY REQUIRES CERTIFICATION UPON INSTALLATION AND RECERIFIGTKIN ANNUALLY. <br />A. TEST COCKS ARE REQUIRED TO BE PLUGGED. mi <br />S. MAXIMUM HEIGHT OF ASSEMBLY FROM FLOOR IS FIVE FEET UNLESS AN OSHA APPROVED PLATFORM IS PROVIDED. <br />6. ALL DIMENSIONS AR MINIMUM CLEARANCE REOUIREMENTS. <br />7. FIRE DEPARTMENT PUMPER CORRECTION MUST BE DOWNSTREAM OF ASSEMBLY. <br />6. NEITHER OS k Y CAN BE USED AS A POST INDICATOR VALVE. <br />DETEM AND LAR(„ERv SERWM I �a-24-96 <br />on 1 omw m w ry IP date number <br />CITY OF EVERETT - PUBLIC WORKS DEPARTMENT <br />