<br />7513 Lighting Controle. LighNng, fnUuding exempl lighqng in
<br />Sedion 1512. shall comply with this sectlon. Where ocwpancy
<br />sansors are ciled, lhey sheV bave Ihe features lisled in Section
<br />7513.6.1. Where autanaUc tlme switches are cited, they shall
<br />have the features listed in Section 7513.6.2.
<br />1513.1 Local Control and Accessiblliry: Each space,
<br />enclosed by walls or.aiting-helght partitbns, shall bo prwided
<br />wilh lighting controls located within ihal spxe. The lighting
<br />rnntro�s, whether one or more, shall be capablo of tuming oR
<br />all li9hts within the spaw. The conirols shail be readily
<br />accessible, al the point of entryfexit, lo personnel xcupying or
<br />using the space.
<br />EXCEPTIONS: 7he (olbwing �ighling conVols may be
<br />cenValized in remole Ixalions:
<br />1. Lighdng conirois fa spaces which musl be used
<br />as a whole.
<br />2. Automatic controis.
<br />3. Conlrols requiring Valned operators.
<br />4. Conlrols lor salety hazards and security.
<br />1573.2 Area Controls: The maximum IighUng power lhal may
<br />6e controlled Irom a single swit:h or automatic wntrol shall not
<br />exceed ihat which is provided by a lwenly amperr. circuit
<br />�oaded lo mt more than eighry pe.rcenL A m;.: ter conVoi mey
<br />6e Installetl prwided the individual swilches retain their
<br />capability W lunction independenlly. Cimuit hreakers may not
<br />be used as lhe solo means of swilching.
<br />EXCEPTIONS:
<br />1. Industrial or manulacturing process areas, as
<br />may 6e requiretl la produdion.
<br />2. Areas less Ihan 6!e percenl of footprinl for
<br />footprinis over 100,000 square leel.
<br />1513.3 Daylight Zone Control: All daylighted zones, as
<br />defined in Chapter 2. both under overhead glazing end
<br />adjacent lo verlical glazing, shall be providetl with indNidual
<br />controls, a r:aylighl-or ocaipen4sensing aulomalic controls,
<br />which contrul �he IigMs independenl of general area lighling.
<br />ConGq�ous daylight zones adjacent to vertical glazing are
<br />ullowc,i :o be contmlied by a single controlliny device provided
<br />Ihat lhey do not inciude zones facing more ihan lwo adjacent
<br />cardinal orienlations (i.e. north, east, soulh, wesl). Daylight
<br />zones under overhead glazinq more Ihan 15 feel from lhe
<br />porimeter shall be controlled separateiy Irom dayliqhl zones
<br />adjacent to vertical glazing.
<br />EXCEPTION:
<br />Daylighl spaces enclosetl by walls or ceiling
<br />heigh� pertitions and canlaining 2 or fewer lighl
<br />fixWres are not r[puired to have a separate swilch for
<br />general area lighting.
<br />1513.4 Display, Exhibitlon, and Speclally Lighting
<br />Controls: All display, exhibition, or specially Iighling shall be
<br />conlrolled independently of general area lighting.
<br />li9hting not intended for 24-hour contlnuous use shaM be
<br />aulomaticaly switched by timar, pAotocell, or a combinatlm of
<br />timer and photocell. Aulometic time nwilches must elso have
<br />program back-up capebilities, which prevent Me bss of
<br />pmgram and time settings tor al Ieast 10 hours, H power is
<br />interrupted.
<br />1573.6 f:utomatle ShutAR Controla, lnterlor. OHke
<br />buildings grealer Ihan 5,000 sq. N. and all school classrooms
<br />sAatl be equipped wilh separate automalic controls to shul ofl
<br />lhe Iighting during unoccupied hours. AulomaNc conVols may
<br />be an xcupancy sensor, time switch, or olher tlevice capa6le
<br />of automatirally shulling ofl lighting.
<br />EXCEPT10N5:
<br />1. Areas that must be cantinuously illuminatad, or
<br />illuminaled in a ma�ner requirirg manual
<br />operation ol lha lighling.
<br />2. Emergency Iighling systems.
<br />3. Swilching for industrial or manufacturing prxess
<br />facililies as may be required lor produGfon.
<br />1517.6.1 Oceupaney Sensors: Occupanr.y sensors sAali be
<br />capable ol automatkally tuming oH all the lights in en area, no
<br />mae Ihan 30 minutes afler the area hes been vaceled.
<br />1513.6.2 Automatle Tlme Switehas: Au!omatic time swilches
<br />shall have a minimum 7 day clock end be capahle of being sal
<br />fa 7 diRerent day types per week and Incorporete an automatic
<br />holiday'shuboft" teature, which tums oN all loads for al least
<br />24 hours and Itien resumes normally scl eduled operations.
<br />Automatic time switches shall also have program back-up
<br />capabilities, which prevent the loss of program and time
<br />setlings for al least 70 hours, if power is intertupted.
<br />Automalic Iime owitches shell incorporale an over-ride
<br />swilching tlevice which:
<br />a) is readily uccessible;
<br />h) is located so thal a person using Iha device can see Iha
<br />lighls a the ereas controlled by the switch, or so that 1he
<br />area being illuminated is annunaated; and
<br />c) Is manually operated;
<br />d) allows Ihe lighting lo remain on fa no more than Mo Murs
<br />when an over•ride Is initiuled; and
<br />e) controls an area not exceeding 5,000 square feel or 5
<br />percent of footpnnt for loolprints over 100,000 square feel,
<br />whichPver is grealer.
<br />1513.7 Commissioning Rpuiromanta: Fa lightlng conVols
<br />which include daylighl or occw2nt sensing automatic cootrds,
<br />automaUc shul-olf conlrols, occu+ancy sensors, a autometk
<br />time switches, ihe lighting conlrols shall be tested to ensure
<br />Ihal conirol devices, componenis, equipmenl and syslems are
<br />calibrated, adjusted and oparate In accordance with approved
<br />plans and specificalions. Sequences of operetion shall be
<br />funclionally tested to onsure they operate in accordance with
<br />approved plans and specificatbns. A camptete report of test
<br />procedures and resulis shall ba prepared and filed wilh lhe
<br />owner. Drawing notes shall require canmissioning in
<br />accordanco with this paragraph.