Laserfiche WebLink
Plan Check No. 92/36172 <br />Page Two of Three <br />�l <br />0 <br />The tup of handrails are to be placed not less than 34 inches nor more <br />than 38 inches above the nosing of treads. Section 3306(j). <br />Handrails projecting from a wall must have a space of not less than 1 <br />1/2 inches between the wall and the handrail. Section 3306(j). <br />9. The handgrip port?on of handrails shall be not less than 1 1/2 inches <br />nor more than 2 inches in cross sectional dimension or the ^hape <br />should provide an equivalent gripping surface. The acceptability of <br />equivalent shapes will be determined by the building official. The <br />handgrip portion shall have a smooth surface with no sharp corners. <br />Section 3306(j). <br />10. Handrails must have their ends returned or terminate in newel posts or <br />safety terminals. Section 3306(j). <br />11. Guardr.ils for stairs, balconies, and landings shall conform with <br />Section 1712. Note that maximum clearance between intermediate rails <br />Jis less than 6 inches and guardrail height should be 42 inches, <br />(Guardrails ar. the sides of open stairways may have a height as <br />permitted for handrails). Section 1712. Provide a section through <br />the foyer plant shelf to verify guardrail requirements. <br />12 <br />13 <br />14 <br />�5 <br />� <br />�7 <br />Enclosed usable space under stairs must be protected on the enclosed <br />side as required for 1-Hr fire-resistive construction, Section <br />3306(m). ,�ee a� Section 3309(f). <br />r�� <br />Walls and floor separating dwelling units in the same building shall <br />be of not less than 1-Hr fire-resistive construction. Section <br />1202(b). Specifically at the decks of units three (3) and four (4). <br />i�-� - �-� <br />A G:oup R, Div sion 1 Occupancy more than two stories in height or <br />having more than 3,000 square feet above the first story shall be of <br />1-Hr fire-resistive constructiun throughout Sect:on 1202(b). Provide <br />justifying test data for each assembly shown. <br />q.-g -.� - � A - 6 <br />Garages in connection with Group R, Division 1 Occupancies shall have <br />a minimum unobstructed headroom clearance of seven feet. Section <br />1102(c). � _ � � <br />A Group M, Division 1 Occupancy requires an occupancy separation rom <br />a Group R Division f1/ Occupancy in�accordance with Table No. 5-B. <br />�—b <br />Provide deck details per Sections 1711 and 1707(c). <br />.L�a — � <br />