My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
3723 ROCKEFELLER AVE 2016-01-01 MF Import
>
Address Records
>
ROCKEFELLER AVE
>
3723
>
3723 ROCKEFELLER AVE 2016-01-01 MF Import
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
5/4/2017 10:31:51 PM
Creation date
2/27/2017 2:21:39 PM
Metadata
Fields
Template:
Address Document
Street Name
ROCKEFELLER AVE
Street Number
3723
Imported From Microfiche
Yes
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
65
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
perbix <br />bykonen <br />memorandam <br />Dale: 6/25/08 <br />70: Premium Construction <br />Attn ]im Fagerlie <br />Re: Shear Wall Connections <br />820 John Street, #201, Seattie, WA 98109 <br />phone 206-264-7784tax 206-264-7769 <br />From: Andy Quir <br />Project 3725 Roc <br />Project #: <br />Copy lo: <br />r_^� '__�_._.�.-�--' <br />(� •�Oii�•.,_' ��_Q��' .-..v_� <br />As requested I visited the site and reviewed the permitted construction <br />drawings for the project located at 3725 Rockefeller Ave in Everett, <br />Washington in order to verify the required shear wall connection al the rim <br />joists. Based on my field observations and conversation with the contractor <br />it is my understanding that the connection shown below has been provided at <br />the shear walls. - • � <br />F- --- S W <br />(=- — /,�JU LTP�! C' T/NT /S,FTr�,fF.N <br />` � f 5H�'��rNiv(, <br />% I �--�-- r,nv i� rire,,rr+�u5 <br />`�" r-- Sw <br />It's my opinion that this connection is not adequate to transfer the required <br />IaCeral forces through the floor system. I recommend that framing plates be <br />added at the designated shear walls as necessary to achieve the required <br />shear transfer between floors. Based on the shear wall schedule provided on <br />sheet A3/13 of the approved structural drawings the foliowing connectors <br />should be added. <br />Wall Type Allowable Shear <br />Roof 180 plf <br />floor 215 plf <br />SW1 260 plf <br />SW2 145 plf <br />Required Connection at Rim Joist <br />LTP4 @ 3'-0" o.c. max. <br />LTP4 @ 2'-6" o.c. max. <br />LTP4 @ 2'-0" o.c. max. <br />LTP4 @ 4'-0" o.c. max. <br />If at any location the length of the designated shear wall is less than the <br />spacing specified above provide one LTP4 at each end of the wall. <br />Please call me if you have any further questions. <br />End of inemo. <br />� <br />�� <br />
The URL can be used to link to this page
Your browser does not support the video tag.