f. Where directed by the Fire Code Official, specific areas shall be designated and those <br />areas are to be marked with diagonal striping across the width of the fire lane. Diagonal <br />marking shall be used in conjunction with painted curbs and/or edge striping and shall <br />run at an angle of 30 to 60 degrees from one side to the other. These diagonal lines <br />shall be in red traffic paint, parailel with each other, at least 6 inches in width and 24 <br />inches apart. Lettering shall appear as above. <br />5. Fire Hvdrants - Locations as planned are acceptable. <br />6. Premise Identification - Premises shall be clearly identified by the correct address at the street <br />entry. Buildings shall be clearly identified so as to be visible and legible from the access road. <br />Individual apartments and suites, where applicable, shall be clearly and legibly identified from <br />the access ad. _See EMC 16.03, Section 505.1.'. (Address Posting Policy). <br />mYi�e 10-inch building numbers with 4-inch suite numbers. <br />7. Fire flow for this project is 1,500 gpm. <br />8. Fire Alarm Svstem - An approved automatic fire detection system shall be provided as required <br />by City Ordinance No. 3021-07, Chapter 16.76, of the Everett Municipal Code. <br />Plans for such system shall be submitted to the Fire Code O�cial for review and approval prior <br />to installation. Submittal shall include cut sheets of ali equipment intended for use. Appropriate <br />trip tests, witnessed by a Fire Department Inspector, shall be performed, along with a certificate <br />of completion, prior to final acceptance of the system. <br />Fire alarm systems shall be installed according to NFPA Chapter 72. Installation of fire alarm <br />components, including basic wiring, may not commence before plans are approved by <br />the Fire Department Plan Reviewer. Fire alarm drawings must be professionally rendered, in <br />sufficient detail, and must be internally consistent. Riser diagrams must match installation plans <br />and load calculations. Components must be listed and approved for use together. Changes to <br />plans must include new drawings and calculations and must be approved by the Fire <br />Depaitment Plan Reviewer prior to installation. Fire alarm installation is subject to field <br />inspection by a Fire Dep�. tment inspector. An approved set of pians and the Engineering & <br />Public Services Department electrical permit must be present for any instaliation inspection. <br />Fire alarm systems shall be installed under permit of the City of Everett Engineering & Public <br />Services Department. Glectrical inspections and approval are required prior to calling for <br />acceptance tests. Call (425) 257-8810 for permit information. <br />T;ie absence of working phone lines for the alarm system will be cause for postponing <br />Fire Uepartment inspection and testing and shall result in denial of occupancy. <br />A copy of NFPA 72 Record of Completion form must be filled out prior to final occupancy (NFPA <br />72, 2007 Edition, page 72-33). <br />Call for design requirements per Authority Having Jurisdiction. <br />Automatic smoke detection is required. <br />