PUBL/C /�l/O/�X5 <br /> Februa.ry 3, 1993 <br /> Kelvin Barton <br /> 506 E. View Ridge Drive <br /> Everett, Washington 98203 <br /> RE: Owner: Kelvin Barton <br /> Job Address: 506 E. View Ridge Drive <br /> Plan :,heck No.:39209 <br /> Dear Mr. Barton: <br /> In response ro your application for a conswction F�ermit, your plans have been examined and <br /> you are advised that the issuance of a permit is M:ing withheld for the reasons listed below. <br /> These comments address building issues only, addiGonal revisions o: additions may be <br /> required by other departments (such as Udlities, Planning or Fire). All references refer to the <br /> 1991 Uniform Buildmg Code, as amended by .he State of Washington and/or Washington <br /> State Energy Code 1991, 2nd Edition, unless stated othenvise. <br /> 1. Provide detail showing how 2x12's connect to existing house. <br /> 2. Specify posdbeam, posdfooting, and beam/beam connections. <br /> A positive connection is required to resist uplift and lateral displacement/2516(m). <br /> 3. Specify type of heat used in office addition and the proposed U-Value of any new <br /> wmdows and doors. <br /> 4. Concrete slab is called out as 4 inches thick on Sheet 6 and as G inches minimum on <br /> Sheet 7. Please darify. <br /> 5. Show depth of foodng below finished grade (18 inches minimum required) and height <br /> of footing above finished grade (6 inches *ninimum required). <br /> 6. Insulation baffles are required at each vent. Baffles shall extend 6 inches vertically <br /> above batts and 12 inches vertically above loosefill insulation. <br /> CITY OF EVERETT• 3200 Cedar Street• Everett.WA 98201 • (206) 259-6800 • Faz (206) 2:i9-6856 %`D� <br />