Page I nf4 <br /> C.O.E. # ,Sc,llS6 <br /> Date /Z�Z'7/9S <br /> RESIDENTIAL CORRECTION LIST <br /> 1995 Washington State Energy Code and <br /> Ventilation and Indoor Air Qualiry Code <br /> WSEC <br /> � Please specify, on the drawings, the R-values of the insulation in the roof-ceilings, above grade <br /> walis, below grade walls, floors and slab on grade. <br /> � Specify on the plans the tested U-values, and sizes of the windows, skylights and doors. <br /> 502.1.5, 1006 <br /> � Please provide heat loss calculations and U-values for components of each clement justifying <br /> compliance by the Component Performance Approach. <br /> � Show insulation in all elements between the heated and unheated space. <br /> � Show at least one inch of vent space above the ceiling insulation with cross ventilation. <br /> 502.I.4.5 <br /> Q6 Show the vent bafiles at the eaves and specify a rigid material, resistant to wind driven moisture <br /> extending at least six inches above noncompressed insulation and twelve inches above loo�e fill <br /> insulation. 502.f.4.5 <br /> � Show slab insulation providing a thermal break between the interior and exterior. The insulation <br /> should extend downward from the top of the slab for a total distance of 24 inches or downward <br /> to the bottom of the footing on the exteriur. 502.1.4.8 The detail(s) shown do not comply. <br /> � Provide a ground cover of six mil black polyethylene or approved equal for the crawl space. <br /> Lap edges 12". 502.1.6.7 <br /> �� Specify on the plans that insulation exposed to the exterior shall be protected and listed for that <br /> .J use. 502.1.4.8 <br /> � Specify on the plans the type of vapor retarders to be installed on the wartn side of the insulation <br /> for ceiling, walls and floor. 502.1.6.1 <br /> 11 Note on the drawings that insulation shall be provided with cleazances for venting, chimneys, <br /> lights, etc., in accordance with the manufacturer's specifications. 502.1.43 <br /> � <br />