,i . � � � <br />J. . <br />B. 2�lamn�ablc 7'rash: <br />In bascinent. <br />Actiion Rcquired: I3rin� clectrical systcrn up to mininium code requirciucnts <br />and removc all flammaUlc trasli. <br />4. Inadequatc Firc-Protection. Sca H-1001(n), U.13.C., Vol. III <br />A.. Inoperative Duinb ��i�aiter: <br />Is not enclosed �vith 1 hour fire resi�tant material <br />to prevent spread of fire and sinoke from one ffoor <br />, to anothcr. See Section 1. 4 Fire Prevention Code, <br />Ordinancc N4114. <br />B. Holes In I3asement Ceiling: <br />Not covere y 1 hour ire resistant material. <br />C. Walls of Custodian Quarters: <br />ot covcre y 1 our firqresistant material, <br />D. Glass In I3asemcnt IPire Alarm Station 73rolcmt: <br />ection 1. 3 P'ire Yrevention CocTe — <br />Action Required: <br />ovcr a 1 openings �vhich would perinit fire and s�noke to <br />commwiicate fro.m onc floor or rooin to anotlier floor or room with 1 <br />hour fire resistant material (5/8" sheetrock). 1 hour protection is a minimum <br />in Firc Zone 1 regardless of whetlier Uuilding confoxmed to code wlien <br />constx•ucted. Replace glass in basement fire alarm statio:i so that in case <br />of a fire in the Uasement a perso�i �vould not Uc required to go to tlte first <br />floor to turn in an alarm. � <br />5. Inadequate I�:sts Sec. II-1001(m), U. B. C., Vol, III <br />A. IPire I�ist on Gtli I�loor IQot Available: <br />lloor+Iead�tig to it is oc e. tter oor unlocked, <br />it was noted tl�at such cord �vas brolcen on windo�v <br />leading to fire escape so that �ti�indow �vould not open. <br />See Section 11. 2 Fire Prevention Code, Ordinancc i14114. <br />B. Exit On thc I3ast rnd of the Second T'loor: <br />Is not ma:lced in tlie liall�vay and the door leading <br />to it is lock�:d. Section 11. 1, 11. 2 Fire Prevention <br />Codc. <br />C. Door On 5outh�vcst Corucr Of Dinin IZ� oo�n: <br />��ngs in—%ireciioai of egress so that �t �vould Ue <br />considered a blocked exit in case of fire. Section <br />11. 1 1�'ire Preveution Code. , <br />D, Pxit Signs: <br />un-.inatecTesit signs havc not Ucen installed in t:lic <br />dining room. Not all rcquired illnminated esit signs <br />h a v c b c e n insial] ed in thc dining room, Not all <br />reytiired illluninated exit si�is have Ucen installed <br />at tLc cnd o: ccntcr ]:all�;a5�s p�inting to firc esits on <br />2nd throu�h Gth floors. Section 11. 2].�'ire Prevention <br />Code. <br />Action itequired: <br />, . „ • ' ,. ,. .. <br />j]]SlitC ���a� �iii C:iii.5 �iPQ U(5�ii nii�l Ill&inCC� c"Llit� tu«s JG61'G 5lilii� <br />itt the proper direction. Insure ihat ilic following rcyuired i7ltuninated <br />c�it ligliis are i�istalled oii an emergency circuit: <br />DINING ROOI�L• One lcading to allcy. <br />I�OYlslt: Onc ovcr South dor�r. <br />Ona ovcr \�t�est door. <br />