Laserfiche WebLink
w <br />• <br />Plan Check No. 57048 <br />November 24, 1997 <br />Page 2 of 2 <br />8. All sheets submitted in plan set should be the same size and munbeted sequentially. <br />9. Concealed spaces, such as drop ceilings or soffits, we required to be fireblocked at not more than <br />10'-0" on center horizontally and vertically. <br />10. Guardrails shall be not less than 36" above the walking surface of the deck (see detail #3). <br />11. Footings shall rest on undisturbed soil not less than 12" below the finished grade. <br />12. Detail #6 shows a framed wall on top of existing concrete wall. Show how wood framed wall is <br />connected to concrete will. Show n u imum and maximum height of wood framed wall. Provide <br />double top plate lap splices 48". <br />13. Show how ledger is attached to existing rim joist (see detail #4). Specify size and spacing of <br />connectors. <br />Prepare a response letter showing where each item in this correction letter is addressed on the plan set. <br />Upon resubmittal of the drawings, your application will be given priority &id plan review will recommence. <br />All required submittals shall be of sufficient detail and contain sufficient information to ensure that the <br />proposed structure will be constructed in compliance with all adopted codes. <br />Sincerely, <br />4e /4� <br />Jeff Heilman <br />Development Technician <br />1x:iueMArokk.91 <br />