Laserfiche WebLink
. , <br /> 4�,�.wT.1�/.i � <br /> • ' ` STAIE �F DEPAR7 MENT OF SOCIAL AND HFALTH SERVICFS <br /> � 4.r.SHINGTON oh,,,m;,,wr:h��,�„„,yasw <br /> 5. ` , <br /> �'�+r.,.<ni�` Dixy Lee Ray <br /> riolrnpr <br /> �.'� � June 3, 1980 <br /> Ebby D. Davis, Manager , <br /> Ever-Dale Congregate Care Facility <br /> 2202 Rucker <br /> Everett, Washington gg2pl ; <br /> Re: Ever-Dale Congregate Care facility ' <br /> Fire A)arm i <br /> CRU N80070-16R5-2 � <br /> Dear Ms. Davis: <br /> The following is a review by our staff consultants of the fire alarm � <br /> drawings received May 22, lggp, <br /> The revie�r findings are divided into parts as folloivs: , <br /> STATE ELECTRICAL PLANS EXAMINER'S REYIEW ( <br /> � Fire alarm system plans shall show: <br /> 1. Interconnection of a11 equi�nent. <br /> 2. Types of equipnent used. This shall include brochures of ail <br /> equipment. <br /> 3. Type of conductors used. ��umber of conductors between all potnts <br /> shall be sho►vn. <br /> 4. Connection to primary source and type of secondary or emergency <br /> power source. <br /> i <br /> 5. U.L, listing shall be shown on atl equipment including digital <br /> dteler. <br /> i <br /> � <br /> STATE FIRE MARSHAL'S REVIEW <br /> i 1. Provide a scale drawing. <br /> i <br /> j 2. Show interconnection of all equipment. � <br /> � <br /> 3. Each floor shall be a separate zone on the annunciation panel . <br /> 4. Provide a smoke detector at top of each stairway, <br /> 5. Provide brochures and dlscripttve material on all equipment installed. I <br /> 6. Provide details on type conductors used. ; <br /> � <br />