Laserfiche WebLink
,...._.._._.,� <br /> ��:eii'.�.'i�ti� ` <br /> ` 1 <br /> t <br /> 1 <br /> i <br /> � , . <br /> September 'L2, 1976 <br /> Ihe Evergrcen <br /> CITY OF <br /> Rryant, Butterfield & Frets, Architects eve rett <br /> 717 Medical Dental Building <br /> Everett, Washington 98201 ��*� ��•« . :s•-e,,, <br /> � [VERCTT. WASHINGTON <br /> sezoi <br /> Re erence: Apartment I3uilding for Olson and Prideaux ��s�«*��� DCPAqiHCNT <br /> 2629 Rucker <br /> Type Construction V 1-hour <br /> Occupancy Class Fi h J-1 <br /> Fire Zone 2 <br /> Plan Check No. 76-357 <br /> Gentlemen: <br /> The Plans £or the above referenced project have been compl.eted <br /> and the follocving corrections are required to comply with the <br /> Uniform I3uilding Code. <br /> 1. Nonabsorbent backing for bath and shower walls should ' <br /> comply with Section 1711 (d) . <br /> 2. Exits from second floor. shall have a minimum separation <br /> of one half of the maxi.mum overall diagonal of the <br /> building. Section 3302 (c) . <br /> 3. Openings in occupancy separation wall (between laundry <br /> room and pa.rking garage) shall be one hour fire-rated <br /> assemblies. Section 503 (c) 4 . <br /> 4. Structural columns and beams in parking garage shall <br /> be of one hour fire-resistive construction. Table 17-A. <br /> 5. Water closets ::hall pot be wet vented. U.P.C. Section <br /> 613 (a) . <br /> G. Provide cleanouts in compliance with U.P.C. Section 40G. <br /> 7. Smoke detectars shall be wired so that when actuated a <br /> detector shall provide an alarm audible in every dcoelling <br /> unit. E.Pf.C. #305-74. <br />