Laserfiche WebLink
PUBL/L /�f/G.rrXS a <br /> ������ <br /> k. <br /> April 27, 1993 <br /> Roger Chapman <br /> 3020 Rucker Avenue <br /> Suite 309 <br /> Everett, Washington 98201 <br /> RE: Solberg Recovery Center <br /> BP 23760 <br /> Dear Roger: <br /> Enclosed are copies of the Inspection Report and a portion of the Atrium Code Section <br /> (1715(c)) which addresses openings. <br /> The following is an explanation of the corrections noted on the report. <br /> l. Ducts: As we discussed, those ducts which have openings in the conidor <br /> require a fire damper at the �mint where they penetrate the corridor. Those <br /> ducts that transition to a plastic material also need fire dampers or the plastic <br /> could be changed to metal. <br /> 2. Penetrations: Doors opening into the wrridors require gaskets to prohibit <br /> smoke migration. <br /> 3. Atrium: The windows between the atrium and the office space require wire <br /> glass or a system of sprinklers and gaskets described in the enclosed. code <br /> exempt. <br /> 4. Exit Doors: The corridor doors within the office must be self closing. Hinges <br /> are available witl� a self closing spring. The one door (easterly) which swings <br /> in is supposed to swing inro the atrium. Given the width of the walkway this <br /> requiremen[ will not be required. <br /> I apologize for the tardy response and follow-up. If you have any questions please feel <br /> free to call me at 259-8810. <br /> Sincerely, <br /> Tim Tyler <br /> Building Official <br /> .;nmran <br /> CITY OF EVERETT•3200 Cedar Street • Everett. WA 98201 • (206) 259-8800 • Fax (206) 259-8856 <br />