Laserfiche WebLink
:. <br /> . <br /> ::. � <br /> ,•�:���/I�G . Medica!Gases • Medical Gas Line ��jY()�j �� � <br /> � � <br /> JAN 0 7 2002 <br /> """ MEDICAL GAS LINE VERIFICATION ""* <br /> .......... .................................... <br /> CITY OF EVERETT <br /> Eng�neermp/Public Services <br /> ]9 NOVEMBER 2001 <br /> CONTRACTOR: DIAMGND "B" CONSTRUCTORS, INC. <br /> DATE/TIME OF TESTING: 17 SEPTEMBER 2001 / 10:00 A.M. <br /> 12 NOVEMBER 2001 / 1:20 P.M. <br /> 13 NOVEM1II3ER 2001 /9:20 A.M. <br /> 15 NOVEMBEIt 2001 /3:00 P.M. <br /> � <br /> FACILITY: TRASKEVERETTCLINIC �E'rn�� 'F XG/Op--pL� <br /> AREA(s): OR#1, #2, #3, #4, PRE-OP, RECOVERY AND PEDIATRIC ROOM. <br /> I. GENERAL FIND[NGS: <br /> A.MEDICAL GASES AND VACWM ARE IN COMPLIANCE WITH NFPA 99 <br /> (1999 ed.). LEVEL 2 <br /> B.NO CROSSED LINES WERE FOUND IN MLDICAL GASES OR VACUUM <br /> IN TESTED ARE.4S ON THE DAY OF TESTING. <br /> C. MEDICAL GASES MEET OR�XCEED MINIMUM CONCENTRATIONS. <br /> D.MEDICAL GASES MEET OR EXCEED r11NIMUM FLOVV AND PRESSURE. <br /> E. MEDICAL VACWM MEETS OR EXCEEDS M1NIn7UA4 FLOWS <br /> AND VACUUM LEVEL. <br /> F. b�DICAL GAS SYSTGM C01�1PONENTS IN AREA TESTED ARE IN <br /> COMPLIANCE�VITH NFPA 99 (:999 edJ. <br /> G. MEDICAL GAS LINE PURITY— PASS tl240TAC-1029-A (AL) <br /> II. MEDICAL GASES: <br /> A.OXYGGN: <br /> 1. STATIC LINE PRESSURE: 55 PSIG. <br /> 2. UYNAMIC PREE rLOW: >3.5 SCFM. <br /> .i. �7XYGEN CONCENTRATION: >99.0 %. <br /> 4. llELTA FLOW - PASS. <br /> TRASKC9-17.01 Pg 1 of 2 <br /> 2706 164th Stree[S.W., Lynnwood,WA. 98037 <br /> `�/, // (425) 741•8807 • I•800-736-7047 • Fax: (425) 741-25U0 �/8 <br /> G� <br />