Laserfiche WebLink
� <br />May 16, 2005 <br />Pagc 2 <br />7. The plans should indica[e the requirement, and detailing to accomplish, on-hour fire <br />partitions at walls that separate dwclling units. (IBC 708). These walls must also <br />comply with the sound transmission requirements of IBC 1207. <br />8. Guardrails are required lo be 42" high. (IDC 1012.2). <br />9. 7'he plans should indicate the method of verlical suppoR for Ihe roof trusses above the <br />mastcr bedrooms and grcat rooms. <br />l0.11old-downs specified for "P2-3" shcar walls must Ue adequate (or a rim joist <br />configuration. Please revise. <br />11.7'he plans should include thc requirement for special inspection of the lateral force <br />resisting systent as requircd by thc I13C 1707. <br />Pleasc prepare a response Ictter showing whcre cach item in this correction lelter is addresscd <br />on thc plan sct. <br />Upon resubmittal of the drawings, your application will be given priority and plan review will <br />recommence. <br />All requircd ��v�» �«ais s���u i,� �r s�rr����,c d��ail and contain suflicienl information to ensurc <br />tl�at the prop.ised stnicWre will be construcled in compliance with all adopted codes. <br />Sinccrcly, '� �U <br />W � h 1 <br />� 1� <br />l <br />s�evc n�tiucr • <br />Associalc I:nginccr <br />ni m r�.n����n�s i x,wi.i.rx iwtw.av u�:: zi �r�i�x i <br />� <br />