Laserfiche WebLink
Plan Check hB-435962 <br />June 6, 1994 <br />Page 2 <br />1/6. Vertical reinforcing bars are required in foundation walls. For <br />conventional foundation walls #4 bars at 24" O.C. are acceptable, <br />retaining walls must be engineered. <br />I1171'v 7 Indicate stud spacing for cripple walls and other walls. <br />✓8. The gjardrail at the deck must be 42 inches high. <br />t/9. Foundation vents are required per sec. 2516(c)6. 12.53 sf of vent area <br />is required. <br />1/110. An 18" by 24"minimum acce-s opening is required to the crawl area. <br />6""11. Smoke detectors are required within each sleeping room and outside each <br />sleeping room. Smoke detectors must have a battery back-up power <br />source in addition to the building wiring power source. <br />WV' ✓12. An accessible parking stall is required and an accessible route of travel <br />r�K� from the stall to the ground floor units is required. <br />/13. Please provide energy calculations or the prescriptive insulation values in <br />table 6-1. <br />In order for the processing of your application to continue, it will be necessary to <br />provide the Building Division with two complete new sets of drawings reflecting the <br />corrections requested. <br />Upon resubmital of the drawings, your application will be given priority and plan <br />review will recommence. <br />All required submittals shall be of sufficient detail and contain sufficient information to <br />ensure that the proposed structure will be constructed in compliance with all adopted <br />codes. <br />Sincerel <br />rffr:o <br />fall <br />Associate Engineer <br />jdgM(w4396 <br />CITY OF EVERETT• 3200 Cedar Street • Everett, WA 98201 • (206) 259-8800 • Fax ('06) 259-8856 <br />