Laserfiche WebLink
N <br /> � <br /> ��° �' <br /> k ff � � <br /> � <br /> consulting enginears <br /> 1980 � � n �; � � <br /> February �_�) l L � � �J 1'� � I � <br /> L�, ��� <br /> FEB f� 1980 <br /> City of Everett Engineering Department _.........._._.. <br /> City Service Center <br /> ........C�; i'i ':J; Ei�'ER�T1. <br /> 3200 Cedar Street i ,.;;�;.� �tor'.s �-P�- <br /> Everett, WA 98201 <br /> Attn: Clair Olivers <br /> Associate Engineer <br /> Subject: Water-SprinklercConnection ��GfM ��;� <br /> Gentlemen: '��'� <br /> Per our discussions of January 29, 1980 d today, we have revised the <br /> piping arrangement on the 8-inch fire sprinkler lines where they connect <br /> to the 12-inch water loop. <br /> We now show, proceeding from the 12-inch main toward the building, a <br /> 12"x8" flanged tee in the 12" main bolted to an 8-inch gate valve, a <br /> spool to the 8-inch check valve in a precast concrete vault, then another <br /> spool to th2 8-inch post �Bd�sPr°nklerVconnecthon detailhonbdrawing C-121 <br /> this is shown on the Typ rints of <br /> and referenced at the sprinkler locations on drawing C-8, four p <br /> each enclosed. <br /> If this does not agree with your notes, please advise me immediately, as <br /> the contractor plans to begin installation very soon. <br /> Sincerely, � <br /> �� �1;�-. , <br /> � <br /> � � ,.� . ,.� <br /> Steven Mennet <br /> Civil Engineering Division <br /> SM/dk <br /> Enclosures <br /> cc: Clay Bush - Fluke (dfg. Co. Architects <br /> Barbara Thomas - The McKinley <br /> 700 Iloyd bldg., seattle, wa 98101 (206) 622-5822 <br /> anohorage los angeles portland seattle <br />