A. GENERAL D. RACEWAYS AND BOXES
<br /> isimo
<br /> 1. EXAMINE THE SITE CONDITIONS VERY CAREFULLY AND THE SCOPE OF PROPOSED WORK TOGETHER WITH 1. ALL CONDUIT SHALL BE UL LABELED.
<br /> THE WORK OF ALL OTHER TRADES AND INCLUDE IN THE BID PRICE ALL COSTS FOR WORK SUCH AS 2. ALL EMPTY CONDUITS INSTALLED FOR FUTURE USE SHALL HAVE A PULL CORD. �✓ ����
<br /> EQUIPMENT AND WIRING MADE NECESSARY TO ACCOMMODATE THE ELECTRICAL SYSTEMS SHOWN AND " Your World.Delivered.
<br /> SYSTEMS OF OTHER TRADES. 3. SHEET METAL BOXES SHALL CONFORM TO NEMA OS1; CAST-METAL BOXES SHALL
<br /> CONFORM TO NEMA 81 AND SHALL BE SIZED IN ACCORDANCE WITH NEC UNLESS
<br /> 2. SUBMITTAL OF BID INDICATES CONTRACTOR IS COGNIZANT OF ALL JOB SITE CONDITIONS AND WORK TO NOTED OTHERWISE.
<br /> BE PERFORMED UNDER THIS CONTRACT.
<br /> 3. PERFORM DETAILED VERIFICATION OF WORK PRIOR TO ORDERING THE ELECTRICAL EQUIPMENT AND E. GROUNDING
<br /> COMMENCING CONSTRUCTION. ISSUE A WRITTEN NOTICE TO THE CONSULTANT OF ANY DISCREPANCIES.
<br /> 4. OBTAIN ALL PERMITS, PAY ASSOCIATED FEES AND SCHEDULE INSPECTION. 1. ALL SAFETY GROUNDING OF THE ELECTRICAL EQUIPMENT SHALL BE CARRIED OUT � TO WERTM
<br /> 5. PROVIDE ALL LABOR, MATERIAL, EQUIPMENT, INSURANCE, AND SERVICES TO COMPLETE THIS PROJECT IN IN ACCORDANCE WITH THE CURRENT REVISION NEC. �'�
<br /> ACCORDANCE WITH THE CONTRACT DOCUMENTS AND PRESENT IT AS FULLY OPERATIONAL TO THE 2. GROUND LUGS ARE SPECIFIED UNDER SECTION 3 "CONDUCTORS AND COMMUNICATIONS
<br /> SATISFACTION OF THE OWNER. CONNECTORS".
<br /> 6. CARRY OUT WORK IN ACCORDANCE WITH ALL GOVERNING STATE, COUNTY AND LOCAL CODES AND 3. ALL GROUND LUG AND COMPRESSION CONNECTIONS SHALL BE COATED WITH
<br /> O.S.H.A. ANTI-OXIDANT AGENT, SUCH AS NO-OX, NOALOX, PENEIROX OR KOPRSHIELD.
<br /> 7. PRIOR TO BEGINNING WORK COORDINATE ALL POWER AND TELCO WORK WITH THE LOCAL UTILITY COMPANY
<br /> AS IT MAY APPLY TO THIS SITE. ALL WORK TO COMPLY WITH THE RULES AND REGULATIONS OF THE 4. GROUND ALL EXPOSED METALLIC OBJECTS ON BUILDING EXTERIOR INCLUDING B+T GRP
<br /> UTILITIES INVOLVED. BUILDING TIE DOWN BRACKETS. im
<br /> 8. FABRICATION AND INSTALLATION OF THE COMPLETE ELECTRICAL SYSTEM SHALL BE DONE IN A FIRST 5. PROVIDE LOCK WASHERS FOR ALL MECHANICAL CONNECTIONS FOR GROUND 1717 S.BOULDER
<br /> CLASS WORKMANSHIP PER NECA STANDARD 1-2000 BY QUALIFIED PERSONNEL EXPERIENCED IN SUCHSUITE 300
<br /> WORK AND SHALL SCHEDULE THE WORK IN AN ORDERLY MANNER SO AS NOT TO IMPEDE PROGRESS OF CONDUCTORS. USE STAINLESS STEEL HARDWARE THROUGHOUT. TULSA,OK 74119
<br /> THE PROJECT. 6. DO NOT INSTALL GROUND RING OUTSIDE OF PROPERTY UNE. PH: (918)587-4630
<br /> www.btgrp.com
<br /> 9. DURING PROGRESS OF THE WORK, MAINTAIN AN ACCURATE RECORD OF THE INSTALLATION OF THE 7. REMOVE ALL PAINT AND CLEAN ALL DIRT FROM SURFACES REQUIRING GROUND
<br /> ELECTRICAL SYSTEMS, LOCATING EACH CIRCUIT PRECISELY AND DIMENSIONING EQUIPMENT, CONDUIT ANDCONNECTIONS, REPAINT TO MATCH AFTER CONNECTION IS MADE TO MAINTAIN
<br /> CABLE LOCATIONS. UPON COMPLETION OF THE INSTALLATION, TRANSFER ALL RECORD DATA TO BLACK CORROSION RESISTANCE.
<br /> UNE PRINTS OF THE ORIGINAL DRAWINGS AND SUBMIT THESE DRAWINGS AS RECORD DRAWINGS TO THE
<br /> CONSULTANT. 8. ALL EXTERIOR GROUNDING CONDUCTORS INCLUDING EXTERIOR GROUND RING WA2821
<br /> SHALL #2 AWG SOLID BARE TINNED COPPER. MAKE ALL GROUNDCONNECTIONSEVERETT
<br /> I10.0• COMPLETE JOB SHALL BE GUARANTEED FOR A PERIOD OF ONE (1) YEAR AFTER THE DATE OF JOB AS SHORT AND DIRECT AS POSSIBLE. AVOID SHARP BENDS. THEERADIUS OF ANYANY
<br /> ACCEPTANCE BY OWNER. ANY WORK, MATERIAL, OR EQUIPMENT FOUND TO BE FAULTY DURING THAT BEND SHALL NOT BE LESS THAN 8" AND THE ANGLE OF ANY BEND SHALL NOT
<br /> PERIOD SHALL BE CORRECTED AT ONCE UPON WRITTEN NOTIFICATION, AT THE EXPENSE OF THE EXCEED 90'. GROUNDING CONDUCTORS SHALL BE ROUTED DOWNWARD TOWARD
<br /> CONTRACTOR. THE BURIED GROUND RING. V WALNT TT
<br /> 11. GENERAL CONTRACTOR IS RESPONSIBLE FOR REQUESTING CONNECTION OF COMMERCIAL POWER FROM THE 9. REPAIR ALL GALVANIZED SURFACES THAT HAVE BEEN DAMAGED BY WALNUT
<br /> POWER COMPANY. ELECTRICAL CONTRACTOR SHALL COORDINATE THIS WORK WITH THE GENERAL THERMO-WELDING WITH ERICO T-319 GALVANIZING BAR.
<br /> CONTRACTOR.
<br /> 12. COORDINATE EXACT TELEPHONE REQUIREMENTS AND SERVICE ROUTING WITH LOCAL TELEPHONE COMPANY. 10. ALL GROUND CONNECTIONS SHALL BE APPROVED FOR THE METALS BEING 3200 20TH STREET
<br /> APPLY FOR TELEPHONE SERVICE IMMEDIATELY UPON AWARD OF CONTRACT. CONNECTED.
<br /> EVF.RETT,WA 98201
<br /> 11. ALL EXTERNAL GROUND CONNECTIONS SHALL BE EXOTHERMICALLY WELDED. ALL
<br /> B. BASIC MATERIALS AND METHODS EXOTHERMIC WELDS TO EXTERIOR GROUND RING SHALL BE THE PARALLEL TYPE, i
<br /> EXCEPT FOR THE GROUND RODS WHICH ARE TEE EXOTHERMIC WELDS. REPAIR ALL EXISTING
<br /> GALVANIZED SURFACES THAT HAVE BEEN DAMAGED BY EXOTHERMIC WELDING. USE MONOPOLE
<br /> 1. ALL ELECTRICAL WORK SHALL CONFORM TO THE EDITION OF THE NEC ACCEPTED BY THE LOCAL SPRAY GALVANIZER SUCH AS HOLUB LECTROSOL #15-501. I
<br /> JURISDICTION AND TO THE APPLICABLE LOCAL CODES AND REGULATIONS.
<br /> 2. ALL MATERIALS AND EQUIPMENT SHALL BE NEW. MATERIALS AND EQUIPMENT SHALL BE THE STANDARD 12. CONTRACTOR SHALL NOTIFY AT&T WHEN THE BURIED GROUND RING IS INSTALLED
<br /> PRODUCTS OF MANUFACTURER'S CURRENT DESIGN. ANY FIRST-CLASS PRODUCT MADE BY A REPUTABLE SO THE REPRESENTATIVE CAN INSPECT THE GROUND RING BEFORE IT IS PROJECT NO: 90146.001
<br /> MANUFACTURER MAY BE USED PROVIDING IT CONFORMS TO THE CONTRACT REQUIREMENTS AND MEETS BACKFILLED WITH SOIL. CONTACT: AT&T PROJECT MGR.
<br /> THE APPROVAL OF THE CONSULTANT AND THE OWNER. CHECKED BY: LRT
<br /> 13. FOR METAL FENCE POST GROUNDING, USE A HEAVY DUTY TYPE GROUNDING
<br /> 3. ARRANGE CONDUIT, WIRING, EQUIPMENT, AND OTHER WORK GENERALLY AS SHOWN, PROVIDING PROPER CLAMP OR EXOTHERMIC WELD CONNECTION TO POST.
<br /> CLEARANCES AND ACCESS. CAREFULLY EXAMINE ALL CONTRACT DRAWINGS AND FIT THE WORK IN EACH 14. WHERE MECHANICAL CONNECTORS (TWO-HOLE OR CLAMP) ARE USED, APPLY A •
<br /> ISSUED FOR
<br /> LOCATION WITHOUT SUBSTANTIAL ALTERATION. WHERE DEPARTURES ARE PROPOSED BECAUSE OF FIELDREv DATE DRwN DESEAFrlont
<br /> LIBERAL PROTECTIVE COATING OF AN ANTI-OXIDE COMPOUND SUCH AS "NO OXIDE
<br /> CONDITIONS OR OTHER CAUSES, PREPARE AND SUBMIT DETAILED DRAWINGS FOR ACCEPTANCE. A" BY DEARBORN CHEMICAL COMPANY ON ALL CONNECTORS. A 4/10/14 MDW PRELIMINARY
<br /> 8 4/14/14 SUM PRELIMINARY
<br /> 4. THE CONTRACT DRAWINGS ARE GENERALLY DIAGRAMMATIC AND ALL OFFSETS, BENDS, FITTINGS AND 15. BOND ALL EXTERIOR CONDUITS, PIPES AND CYUNDRICAL METALLIC OBJECTS WITH
<br /> 0 5/16/14 SUM CONSTRlKTION
<br /> ACCESSORIES ARE NOT NECESSARILY SHOWN. PROVIDE ALL SUCH ITEMS AS MAY BE REQUIRED TO FIT A PENN-UNION GT SERIES CLAMP, BLACKBURN GUV SERIES CLAMP OR A BURNDY
<br /> THE WORK TO THE CONDITIONS. GAR 3900BU SERIES CLAMP ONLY, NO SUBS IIIUTES ACCEPTED. 1 5/28/14SMM CONSTRUCTION
<br /> 2 8/1/14 SUM CONSTRUCTION
<br /> 5. MAINTAIN ALL CLEARANCES AS REQUIRED BY NEC.
<br /> 6. SEAL AROUND CONDUITS AND AROUND CONDUCTORS WITHIN CONDUITS ENTERING THE MODULAR CABINETS
<br /> WHERE PENETRATION OCCURS WITH A SILICONE SEALANT TO PREVENT MOISTURE PENETRATION INTO B&T ErriNGINEERING, INC.
<br /> BUILDING.
<br /> 7 SUICDONE INE.SEAL AROUND ALL BOLTS AND SCREWS USED TO SECURE EQUIPMENT TO EXTERIOR OF
<br /> SON--711111
<br /> F
<br /> 8. MAKE NECESSARY CONNECTIONS FOR BATTERY IN EMERGENCY LIGHT FIXTURE. CONNECT EXTERIOR UGHT OF WASy�v e`
<br /> FIXTURE (PROVIDED BY SHELTER MANUFACTURER) TO EXTERNAL JUNCTION BOX. I ),
<br /> •
<br /> C. CONDUCTORS AND CONNECTORS w O " x
<br /> I . /
<br /> �
<br /> 1. UNLESS NOTED OTHERWISE, ALL CONDUCTORS SHALL BE COPPER, MINIMUM SIZE #12 AWG, WITH r J i;i
<br /> THERMOPLASTIC INSULATION CONFORMING TO NEMA WC5 OR CROSS-LINKED POLYETHYLENE INSULATION 'QG 4� �?
<br /> CONFORMING TO NEMA WC7. (TYPES THHN OR THWN). INSULATION SHALL BE RATED FOR 90 CONDUCTORS itt C , L
<br /> SHALL BE COLOR CODED IN ACCORDANCE WITH NEC.
<br /> 2. ALL CONDUCTORS USED FOR GROUNDING SHALL BE COPPER AND SHALL HAVE GREEN INSULATION. 41`s�ONAL
<br /> (, 3. FOR COPPER CONDUCTORS #6 AWG AND SMALLER USE 3M SCOTCH-LOK OR T&B STA-KON COMPRESSION .,
<br /> s,
<br /> TYPE CONNECTORS WITH INTEGRAL OR SEPARATE INSULATION CAPS. FOR COPPER CONDUCTORS LARGER IT IS A NIS ATION OF IIAV FOR AM PERSON.
<br /> THAN #6 AWG USE SOLDERLESS, IDENT HEX SCREW OR BOLT TYPE PRESSURE CONNECTORS OR DOUBLE UNOF A MOWER.
<br /> P I COMPRESSION C-CLAMP CONNECTORS, UNLESS SPECIFIED OTHERWISE ON DRAWINGS. TO ALTER TNS OOD, 41.
<br /> 4. UNLESS NOTED OTHERWISE ALL LUGS SHALL BE TIN PLATED COPPER, TWO-HOLE, LONG BARREL, SHEET NUMBER REVISION:
<br /> w COMPRESSION TYPE.
<br /> 5. CONDUCTOR LENGTHS SHALL BE CONTINUOUS FROM TERMINATION TO TERMINATION WITHOUT SPLICES. G-1 2
<br /> 6 SPLICES ARE NOT ACCEPTABLE. IF SPLICES ARE UNAVOIDABLE PRIOR APPROVAL FROM THE ENGINEER
<br /> °' MUST BE OBTAINED.
<br /> 7f i2-
<br />
|