. ' ( t� ; <br /> Ltr.J.Fullwiler(B0204-020) <br /> April 19, 2002 <br /> Page 4 <br /> 3. The WATTSUN calculations require R-38 joist insulation. R-38 insulation is <br /> approximately 12-13 inches thick with a joist cavity space of 11-7/8. As the <br /> insulation is not allowed to be compressed, it should be shown how this will be <br /> accomplished. <br /> The master bathrooms should be shown to have minimum 50 cfin exhaust fans. <br /> Section 302.2.1, WSVIAQ <br /> The individual room outdoor air inlets as required by Section 302,3.5.5 of Ihe <br /> WSVL4Q should be shown on the plans - or other options as allowed under <br /> Section 302?.5. <br /> �Each whole house fan should be noted to have a sone rating of 1.5 or less. <br /> Section 303.4.1.2 WSVIAQ <br /> r Structural ' <br /> l. The building has �:n i[regular lateral load resistance path (cant.ilevered horizontal <br /> diaphragm) and therefore conventional constiuction bracing dces nut apply. <br /> Swctural plans, details and calculutions must be prepared and submitted by an <br /> engineer or amhitect licensed 6y che Statz of Washington for the lateral force . <br /> resistance system. Section 2320.5.4.2 � <br /> i <br /> 2. Lateral resistance should be detailed for the attached carport and entry porches. � <br /> 3. The second floor framing plan and detail on �heet 3 should show the candlever I� <br /> eonsuuction and Mfgr's required blockin.g and web stiffeners. As this is not <br /> convenuonal consuvction, an engineer from the joist Mfgr must approve the <br /> design (to include the length of overhang). <br /> 4. Beams should be shown supporting the second story bearing walls (overhang) at • <br /> the garage. Calculations and details should be provided. <br /> 5. The reaz elevation shows 5 posts supporting the second story, whereas the <br /> foundation plan shows 3. The intent should be clarified. <br /> 6. The beam to wall (carport roo�, post to beam and post to concrete connections <br /> should be rietailed on the plans. Any required hardware shouid be specified. <br /> 7. All t]oor and roof plate heights should be shown. <br /> 8. A detail for the slab-on-grade option should be pmvided. <br /> � <br />