Meg Haley <br />From: Meg Haley <br />Sent: Thursday, November 02, 2006 4:59 PM <br />To: 'Adam@GaryParkinson.com' <br />Cc: Steve Miller; Shellie Pons <br />Subject: First Baptist Church Mechanical Submittal M0610-068, 3120 Wetmore Avenue <br />Attachments: 0950 001.pdf <br />Adam, <br />Thanks for taking my call to�ay. I have attached some excerpts from the mechanical submittal that show ducts <br />penetratiny more than two occupied floors (along column line B-2). Ted Budden, our Chief Inspector noted the penetration <br />at B-2 after a field inspection last week. There may be other similar conditions. We released the mechanical submittal <br />today for permit. <br />Please copy us with architectural drawing revisions to accommodate the mechanical system as designed, oi have the <br />mechanical contractor submit a revised layout as required to meet the intent of IBC Section 707.2, Shaft Enclosures. <br />Thanks :or your offer to contact the General Contractor lo expedite resotution of this issue. <br />lJl� <br />0950_OOl.pdf (399 <br />KB) <br />Sincerety, <br />Meg� }ia iey <br />City of Everctt <br />3200 Cedar Shee; <br />Everett, WA 99 �U i <br />Ph: 4.'S�25 i -ud i? <br />Faz: A25�257-BBSF <br />mhalevCadci.everettwa. us <br />www.everettwa.ora/default.asox?I D=376 <br />