Laserfiche WebLink
,, ... SL�ER <br /> . � � . ARCHITECTURE <br /> 'r� . � <br /> City of Everett Public Works Job#9706 <br /> 3200 Cedar Street Oclober 18, 1999 <br /> ,; , <br /> Everett, Washinglon 98201 <br /> RE: Timber HIII Drive Apartments <br /> ; , 7802 Timber Hfll Drfve <br /> �� Plsn Check No. B8808-002,003,001 <br /> Dear Torry Lee and Steve Miller, <br /> The following are the responses to your review comments, dated September 30, 1999: <br /> � ,NON STRUCTURAL <br /> ` General: <br /> 1: The covered car v�ash plans were added to sheet A-2,to be a part of this permit. <br /> 2. 3moke detedors were added to the floor plans on sheel A3. <br /> 3. A nde was added to the floor plan notes for the smolce detectors to be hot wired. See sheet <br /> A-3. <br /> 4. A note was added to the electrical plan notes to call out the exhaust fan size. See sheet A- <br /> 10. <br /> 5. A note was added to ihe Boor plan notes for the whole house veMilation. See sheet A-3. <br /> 6. A note was added to the floor plan notes for the water heater anchorage. See sheet A-3. <br /> Construction: <br /> 1. ' Detail 9/A-8 was added for the vent duct so�t. The vents do not penetrate the rated <br /> assembly, therefore do not require dampers. <br /> 2. Detail 8lA-8 is onty used at the sprinkler riser rc�oms. See wall section 9/A�B.A note was <br /> ' addqd to show that this roof section oniy t�uires ventirg at the eaves. <br /> 3., The plan notes were revised to Indicate pressure treated plywood at the deck slabs. See <br /> details 3/A-5,8 8 7/A�: <br /> ' Exiting: ' <br /> � <br /> , 1, Wing walls were added to the froM of the slair enclosure in order to mafntain a 10 foot <br /> minimum horizontal distance to the emergency egress windows. See walls added to sheets <br /> A-3,4, 7, 8, 10, S-1, 2, 3. <br /> 2. Per UBC section 605.6.4,the 8X8 beam called for has a 4'minimum width and a 6" <br /> minimum depth,which constHules a Heavy Timber member. Thus, it is elready 1-taur rated. <br /> 3. Note#13 was added to the door schedule, and to door numbers 101 and 201,for the fire <br /> „ . <br /> ratfng speGfled. <br /> ; • , <br /> ISSU SE 18'hCircic Vancmivcr,WA 98G83 ;r'- � �/L <br /> Phone: (3C0)8ft3-11525 �as: (360)883-0528 �-: . � <br /> , , • ,i ,t ' . <br /> �. M1 :.ie���.,�tky�f � �. r I 1� �;� �� : i �5� �: � .- ' � �°' L ]a� t t <br /> 1:�� + er�'Fq.(^7�.�' �t S'�l� 1 -.:5 � �� '-� Vf r.�Y j � ����4;(��y.4,�� - u^f Y� yl.e t �r 1 � �� <br /> rl$T..�aRStiY .�Ii�;� SL :. �;yM1�'�� i,. `ii h�tY�j� W �s �'n�ip�".y!( f�p�V��.��':i� �7',.� t{�\ . . .. <br />