Laserfiche WebLink
i� <br />;-- <br />; J <br />a--� <br />�J . <br />Plan Check No.: 92/36180 <br />Pa�;e Three of Thrae <br />15. Framing plans nre not complete ehe basemene plan does show size and <br />spacing oL the floor joLsts at the fizs[ floor level, however it does <br />not shov any of the cantilevcred areas or any interior beems. There <br />are several significant point loads thet are noe addressed on the <br />plans. <br />16. Steirs section does noe shov sufficient deteil [o indicate <br />construc[!on o[ code complLen^e. <br />17. Plans da not shov required smoke detectors as specified in Sectlon <br />1210 of thu UBC. <br />18. Plans do noe provide details of freming of o[her ehan "typicel" <br />conditions. Provido sections at connection of cnntileve[ed floor <br />joists and deck, typical wall section at garage, post end beam in <br />cravl space at retalning vall. <br />19. Plans do not shov how attLc and enclosed raftor spaces are ventilated <br />per Section 3205(c) UBC. <br />20. Provide engineers or architects stamp for structural design of this <br />residence. <br />In order for the processin� of your applLcation to continue, it vill be <br />necessary to provide che Bi:llding DepartmenC wich tvo complete nev sees of <br />drawings zeflecting che corrections requested. <br />Upon re-submiteal oE the draaings, yo�r application will be given pri.ority and <br />plan xeviev vill cecommenco. <br />All required submittals shall be oF sufEicient detall and contain sufficien[ <br />informa[ion to ensure that the proposed ser�cture will be conserucced in <br />compliance vi[h all adop[ed codes. <br />Sin�c/e[ely, <br />Jeff� lman <br />Engineering Technician <br />JHm{Ibldl].16 <br />