Laserfiche WebLink
3haun M`Garry � <br /> Plan Check No. 57835 <br /> February 19, 1998 <br /> Page 2 of 3 <br /> 9. Providc a section of [he brick veneer including foundation support and dimensio�s. Show the <br /> following: <br /> a. A 1" airspace Ue[ween the veneer and backing, 15# felt and minimum No. 9 gauge approved <br /> type non-corrosive ties at 1 for each 2 sq. ft. oF wall surface. Weep holes at the lowest <br /> course. (1403.6.4.2.1) <br /> b. A maximum stud spacing of 16" on center for [he wall anchoring the brick veneer. <br /> (1403.6.4.2) <br /> c. Show brick on floor plan. <br /> d. Construction of the brick column. Provide reinforced construction unless it is designed as a <br /> ��eneer over a structural column. <br /> 10. A door may swing over a landing that is not more than 1" beiow Ihreshold. (1004.9) <br /> 1 I. Provide detail of attic ventilation type, size, and location. Show the required ne[ area calculations <br /> assumi*�g approximately 75% of the vent area is net area unless the actual net area is given frcm <br /> the s?-.anufacturer. The required ventilation area ra[io is 1/150 of the attic area or 1/300 of attic <br /> area if at lcast half of the vent area is more than 3' above eave vents (providing the remainina <br /> portion of the vent area). Opening to have 1/4" (6.4mm) conosion, resistant metal metal <br /> covering. (1503.3) Vented blocking shall not compromise the s[ructural integrity of shear <br /> transfer, roof diaphragm to she:ir wall. <br /> 12. Show under floor ventilation opening size and locations equal to 1 sq. ft. for each I50 sq. ft. <br /> (0.076m' for each IOmZ) of under floor area. Openings shall be as close to corners as practicable <br /> and shall provide cross ventilation along the length oF at least [wo opposite sides. Openings shall <br /> have 1/4" (6.4mm) corrosion resistant metal mesh covering. Show the required net area <br /> calculation assuming approximately 75% of the vent area is net area unless [he ac[ual net area is <br /> given from the manufacturer. (23I7.7) <br /> 13. A ridge board, valley and hip members not less in depth than the cut and of the rafter is required. <br /> It shall oe a venical load-bearing member when roof slope is less than 3" in 12". (2326.123) <br /> 14. Show nll posts on plan including built up 2x's and window header cripples. <br /> 15. Note on framing plans: "Double joists :ue required under pazallel bearing partitions." (2326.8.5) <br /> 16. Detail (and reference location on foundation plan) typical foundation sections for. perimeter <br /> walls, interior bearir.g v�alls, depressed slabs, foundation common to dwelling and garage, gazage <br /> entrance, spread and/or post pads. <br /> 17. Show minimum 18" (=157mm) from grade to bottom of floor joist and minimum 12" (305mm) ro <br /> bottoin of girdcrs. (23173) <br />