Laserfiche WebLink
� � ; <br /> 8. Each bedroom should indicate an em?rgency escape and rescue window opening, meeting the requirements of <br /> IBC section 1029.1,with a reference to an rlevation of the window meeting the requirements of IBC section <br /> 1029.2. <br /> a. P�ease reference clouded notation on bottom of sheet 52. All forms of egress have been dimensioned <br /> and labeled (unclouded for legibility). <br /> 9. Single or multiple-station smoke alarms should be shown on the drawings on the ceiling or wall outside of each <br /> separate sleeping area in the immediate vicinity of bedrooms, in each room used for sleeping purposes, and ir. <br /> each story within a dwelling unit, per IBC section 907.2.11.3. <br /> a. Please note (unclouded for legibility)smoke alarm locations within each unit on sheet 52. <br /> 10. The smoke alarms shc uld be noted on the drawings as being interconnected so that the activation of one alarm <br /> will activate all of the alarms in the individual unit, per IBC section 907.2.113. <br /> a. Please reference clouded note reference smoke alarms on sheet S2 below 1"floor plan. <br /> 11. The power source for the smoke alarms should be noted on the drawings as hard-wired with a bat:ery backi�p <br /> per IBC section 907.2.11.4. Note:this will require an electrical permit application. <br /> a. Please reference clouded note reference smoke alarms on sheet S2 below 1"floor plan. <br /> b. Noted. Electrical contractor is aware of their permit requirements and will seek a separate electrical <br /> permit. <br /> I <br /> , <br /> 3 <br /> �---��,-�-- — _ ----, <br />