Laserfiche WebLink
i <br /> � <br /> i <br /> F'age if 1 <br /> SEPA 75-69 REVISED <br /> EFD PC #89-332 ( SEE EFD PC# 89-164 ) <br /> 47TH & GRAND ( VACATED ) <br /> CHARLIE MORGAN <br /> 120 UNIT , 4-STORY APT BLDG � <br /> T0 : JUSTIN OSEMENE � ,/ ,� <br /> FROM� SAM PRESTON � ��j°� <br /> DATE : 10-5-89 P'; ,�� <br /> �_���, <br /> 1 . FIRE FI.OW - BASED ON 85 , 913 5� FT - TYPE V 1-HOUR , � <br /> SPRINKLERED . 2575 GPM . <br /> 2 . HYDRANTS - 3 HYDRANTS WITHIN 200 DRIVING FEET OF THE <br /> BUILDING . FIRE DEPARTMENT SPRINKLER CONNECTION TO <br /> BE LOCATED NOT MORE THAN 100 ' FROM A HYDRANT . <br /> 3 . SPRINKLcR SYSTEM - PROVIDE A SPFINKLER SYSTEM COMPLYING WITH <br /> UNIFORM BUILDING CODE STANDARD 36-1 <br /> THROUGHOUT THE BUILDING . <br /> 4 . FIFE ALARM SYSTEM - AN AUTOMATIC FIRE ALARM SYSTEM COMPLYING <br /> WITH UNIFORM FIRE CODE STANDARD 14-1 MUST BE PROVIDED IN <br /> EACH MULTI-FAMILY BUILDING OF 3 OR MORE STORIES OF: <br /> CONTAINING 16 OR MORE DWELLING UNITS . <br /> PLANS MUST BE SUBMITTED TO THE FIRE FRE'JENTION BUREAU FOR <br /> APPROVAL . SUBMITTAL SHALL INCLUDE CU1' SHEETS OF ALL <br /> EDUIPMENT FOR USE . APPROPRIATE TRZP TE5T5 MUST BE <br /> PERFORMED AND WITNESSED BY THE FIRE PREVENTION BUREAU <br /> PRIOR TO ACCEPTANCE . CALL 259-8710 FOR ACCEPTANCE TESTS . <br /> FIRE ALARM SYSTEMS MUST BE INSTALLED UNDER PERMIT OF THE <br /> CITY OF EVERETT BUILDING DEPARTMENT . INSPECTIONS AND <br /> APPROVAL ARE REOUIRED PRIOR TO CALLING FOR ACCEPTANCE <br /> TESTS . CALL 259-8810 FOR PERMIT INFORMATION . <br /> ( SPECIAL NOTE ) A SEPARATE FIRE ALARN! SYSTEM NEED NOi BE <br /> INSTALLED IN BUILDINGS WHICH ARE PROTECiED 1'HROUGHOUT EY <br /> AN APPROVED SUPERVI�ED FIRE SPRINKLER SYSTEM CONFORMING <br /> TO THE BUILDING CODE AND UNIFORM BUILGING CODE STANDARD <br /> 38-1 AND HAVING A LOCA� ALARM TO NOTIFY ALL OCCUPANTS . <br /> HOWEVER . ANY SPECIAL FIRE ASSEMBLIES WHICH ARE RESiRAINED <br /> BY A PRCDUCTS OF COMBUSTIONS DETECTZON DEVICE MUST BE <br /> CONNECTED TO THE LOCAL ALARM WHICH WILL BE PROVICED WITH <br /> THE SPRI;�KLER SYSTEM . <br /> 5 . FIRE LANES - FIRE LANES MUST BE PROVIDED AS RE�UIRED IN <br /> EVERETT MUNICZFAL CODE 46 .44 . FIRE LANES MUST <br /> BE IDENTIFIED BY RED CURBS WITH WHITE STENCIL <br /> STATING `NO PARKING - FIRE LANE ' . VERTICAL <br /> SIGNS STATZNG 'NO PARKING - FIRE LANE - <br /> VIOLATORS MAY BE TOWED ' TO dE LOCATED AS <br /> APPROVED B'," THE FIRE MARSHAL . <br />