Laserfiche WebLink
. ( ( <br /> � <br /> � �, <br /> � <br /> F R A N K L I N :�� F��-:�� f,��o���� �- -�� a2�-332� <br /> Suice 202 =AX 425 &27-6252 <br /> ENGINEERING � -� ;�� :��; G,��:, ������:r3�t ,-��, ���n <br /> MECFIANICP,L CONSULT�r1G <br /> June 22, 2010 <br /> ENVELOPE SUMMARY <br /> RE: Advanced Vapor Tech - Mezzanine <br /> Bldg A, Seaway Lot 3C <br /> Everett, WA <br /> Conversion of existing Warehouse area into conditioned Mezzanine space. Project <br /> complies with 2006 WSEC using the Component Performance approach with heating by <br /> Other Fuels. <br /> Vertical Glazing (Exterior): Double pane, 1/2" space Air, low-e10�70j, fixed. Or certified <br /> tested assembly per NFRC. U=0.55, default (Table 10-61. SHGC=0.45. <br /> Vertical Glazing (Re-Iite1: Double pane, any size air space. Or certified tested assembly <br /> per NFRC. U =0.90, default (Table 10-61. SHGC=exempt. <br /> Other Roof #1: R-30 batt insulation on T-bar ceiling. U =0.037, calculated. <br /> Wall #1 (Opaque, Exterior, Floor to 9'-0" AFF►: Concrete, min. 6" thick, furred with metal <br /> studs, 3-1 /2", 24" oc with R-13 batt insulation, U =0.107, calculated. <br /> Wall #2 (0paque, Mezzanine to Warehouse►: Wood studs, 2x6, min. 16" oc with R-21 <br /> batt insulation, U=0.057, default (Table 10-5). <br /> Wall #3 (Opaque, Demisingl: Metal studs, min. 5-1/2", 24" oc with R-21 batt insulation, <br /> U =0.09, default (Table 10-5A1. <br /> Please note that these values are minimum insulation requirements for code compliance. <br /> Higher insulation values may be installed. SHGC = Solar Heat Gain Coefficient <br /> .\ <br /> �� ��.� � <br /> _i! <br />