• 2004 Wa���n ton State Nonresiden6al Ene Code Com ���nce Fortn
<br /> • • • •
<br /> 2o0A wasninglon S�aie Nonresieential EnerBr GmJe Canpiance Forms ReviseE May 7005
<br /> Lighting - General Requirements �5�3.6 Automatic Shut-Off ConVola,Intarior: BuilOings
<br /> 1513 LI htln Controls. Li htin g exem t li htin 9reater than 5,000 sq.tl.antl all schoo�classrooms shall be
<br /> g g g g, includin P 9 9 equippetl with separale automatic controls to shut ott the
<br /> In Section 1512, shail comply with this section.Where liqhting during unoccupied hours.Within these builtlings,all
<br /> occupancy sensors are citetl,they shall have lhe features oNce areas less than 300 ft�enclosed by walls or ceiling-
<br /> listetl in Section 1513.6.1.Where automatic time switches are height partitions,and all meeting and conterence rooms,and
<br /> cited,they shall Y.ave the features listed in Section 1513.6.2. all school classrooms.shall be equipped with occupancy
<br /> �5�3.1 Local Cc�ntrol and Accesalbllity: Each space, sensors that comply Section 1513.6.�. For other spaces,
<br /> enclosed by walls or ceiling-height partitions, shall be provided autcmalir_�onlrols may be an occupancy sensor,time switch,
<br /> with lighting controls located within that space.The lighting or other device capa6le of automatically shutting ott lighting.
<br /> conlrols,whelher one or more, shail be capable ot turning oH EXCEPTIONS:
<br /> all lights within the space.The controls shall be reatlily 1. Areas that musl be continuously illuminaled(e.g..
<br /> accessible,at lhe point of entry/exit,to personnel occupying or 24-hour convenience stores),c+r iiluminated in a
<br /> using the space. manner requiring manual operation of the
<br /> EXCEPTIONS:The fo�lawing lighting controls may be lighting.
<br /> ceniralized In remote locations: 2. Emergency lighting systems.
<br /> 1. Lighling controis for spaces which must be used 3. Swi�ching for in0ustrial or manufacturing process
<br /> as a whole. facilities as may be requiretl for production.
<br /> 2. Automatic controls. 4. Hospitals and laboratory spaces.
<br /> 3. Conirols requiring trained operators. 5. Areas in which metlical or Gental tasks are
<br /> 4. CoNrols for safery hazaiUs and security. perlormetl are exempt from the occupancy
<br /> 15'13.2 Area Controis:The maximum lighling power that may sensor requirement.
<br /> be controlletl from a singie switch or automatic contn�l shall ne,t �513.6.7 Occupancy Sensors: Occupancy sensors shall be
<br /> exceetl lhal which is providetl by a twenly ampere ci�cuit �Pabie of automaticaliy turning oH a�!the lighls in ar�area, no
<br /> loadetl to nol more than eighty percent.A master cuntro�may more than 30 minutes after the area has been vacatetl. �ighl
<br /> be instal�etl provitletl lhe individual switches retain their fixWres co�lrolletl by oxupancy sensors shall have a wall-
<br /> capability to function intlepentlently. Circuit breakers may not
<br /> be usetl as ihe sole means of switching. mounletl,manual switch capable of turning ofl lights when the
<br /> EXCEPTIONS: space is occupied.
<br /> 1. Industrial or manutacturing process areas,as �513.6.2 Automatic Tima Switches:Automatic time switches
<br /> may be required for protluclion, shall have a minimum 7 tlay clock antl be capable of beiny set
<br /> 2. Areas less lhan tive percent ol foolprint for for 7 tlifferent tlay types per week and incorporate an
<br /> footprinis over 100,000 square feet. aulomatic holiday"shut-oH"feature,which tums ofl ali loatls for
<br /> at least 24 hours and then resumes normally scheduled
<br /> 15�3.3 Daylight Zone Control:All tlaylighted zones, as operations.Automatic time switches shall also have program
<br /> tlefined in Chapler 2, both under overhead olazing anC back-up capabilities,which prevent the Ioss of program and
<br /> adjacent to vertical glazing, shall be provitled with indiv�dua� �ime settings fcr at leasl�0 hours, if power is interruptetl.
<br /> controls,or daylight-or occupanFsensing automatic controls, Au(omalic time switches shall inwrporate an over-ride
<br /> which con[rol ihe lights independenl uf generai area lighting. switching tlevice which:
<br /> Contiguous daylight zones atljacent to vertical glazing are
<br /> allowetl to be controlletl by a single controlling device provitled a) is readily accessible;
<br /> that they tlo not inGude zones facing more than two adjacent b) is located so that a person using lhe tlevice can see lhe
<br /> cardinal orientalions(i.e. north,east, south,west). Daylight lights or the areas controlletl by the switch,or so[hat the
<br /> zones under overheatl glazing more than 15 feet from the area being illuminated is annunciated;antl
<br /> perimeter shali be controlled separate�y from tlaylight zones �) �s manually operated;
<br /> adjacenl to vertical glazing. U) allows the lightin�to remain on for iw more than two hours
<br /> when an over-ride is initiatetl;antl
<br /> EXCEPTION: e) controls an area not exceetling 5,000 square feet or 5
<br /> Daylight spaces enclosed by walls or ceiling percent of footprint for footprints over�00,000 square feet,
<br /> height partitions and containing 2 or fewer ligh� whichever is greater.
<br /> fixtures are not requiretl to have a separate swilch lor �513J Commissloning Requirements: For Iighting conirois
<br /> general area ii3hting. whlch include daylight or occupant sensing automalic controls,
<br /> �513.4 Display, ExhlbiUon,and Speclalty Lighting automatic shut-off contro�s,occupancy sensors,or automatic
<br /> Controls:All display, eRhibition, or specially lighting shall be time switches,the iighting controls shall be tested to�nsure
<br /> controlletl intlependr�illy of general area lighting. that control devices,components,equipment and systc.�is are
<br /> �5�3.5 Automatic Shut-Off Controls, Exterior. Exterior calibra�ed,adjusted and operate in accortlance with approvetl
<br /> lighting not intentled for 24-hour continuous use shall be plans and speciflwtions. Sequences of operetion shall be
<br /> aulomatically switched by timer,photocell,or a combination M (unctionally tesletl to ensure they operate in accortlance with
<br /> timer antl photocell.Automatic time switches must also have approved plans and specifications.A complete rrport ot tesl
<br /> prograin back-up capabilities,which prevenl the losn�f procedures and results shall be prepareC and fitetl with the
<br /> prog�am and time settings for a�least 10 hours, it f-=�'+cr is ewner. Drawmg notes shall require commissioning in
<br /> interrupted. acc.irtlance with ihis paragraph.