' 2001 Washin ton S'tate Nonresidential Ener Code Compliance Farm
<br /> • • • •
<br /> 2001 W uNrgton Stele NonreelCer�lel ErorpY Code Comoliencn Fnrms �-- fle�MM Juro P002�IUM
<br /> Lighting - General Requirements 1513.5 Autometk Shut•OH Controls,Extxlor: Exlerior
<br /> 1513 LI htln Controls. U hlin g ezempt lighting in �ightlng nol intendad for 24-hour condnuous use shall be
<br /> g g g g,includin automatically switched by timer,photocell,or a combination of
<br /> Sec�ion 1512,shall comply wilh this seclion.Where ocwpancy timer and photocell.Automatic time switches must also havo
<br /> sensors are cited,ihey shall havo ihe fealures listed in Seclion progrem back•up capabilities,which prevenl the loss ol
<br /> 1513.6.1.Where au�omatic lime switches are citod,they shall program and time settings lor at�east 10 hours,il power is
<br /> have ihe features Iisied in Seotion 1513.62. intorrupted.
<br /> 1513.1 Locel Control end Accesslblllty:Each spaco, �513.6 Autometic Shut-Off Controls,Interior:Oflice
<br /> enclosed by walls or ceiling-hoight parti�ions,shall be provided ��Idings greater thnn 5,000 sq.fl. and all school classrooms
<br /> with ligh�ing controls located within tha�space.Tho lic�hting shall be equipped with separeto autcmatic ccr;rot;tc�kut off
<br /> con�rols,whether one or more,shall bc oapable ot tuming off (he lighlin9 during unoccupled hours.Aulomatic coNrols may
<br /> all lighls wi�hin�he s�iaco.The controls shall bo readily (�an occupancy sensor,time switch,or other device capable
<br /> acces.^,ible,at the point ol enlry/exii,to personnol occupying or of automatically shutling off lighting.
<br /> using�he apaco. E%CEP'fIONS:
<br /> EXCEPTIONS:Tho lollowinc�ligtiting conlrols may bo �. Aroas that must be continuously illuminated,or
<br /> ceniralized in remote locations: illuminated in a mannor requiring manual
<br /> 1. Lighling con�rols for spaces which mus�bo used opc�ra�ion of the lightin�.
<br /> as a whole. 2. Emargency lighting sys�ems.
<br /> 2. Auloma�ic conlrols. 3. Switching for indus�rial or manuladuring process
<br /> 3. Conlrols roquirinc�trained operalors. facili�ies as may be required for production.
<br /> 4. Controls for sa�ety hazards and securiry.
<br /> 1513.2 Area Controls:Tho maximum lighling power lhat may �513.6.1 Occupency Sensors:Occupancy sensors shall be
<br /> be conlrolled from a single swi�ch or au�omatic control shall no� capablo ol automatically tuming off all the ligh�s in an area,no
<br /> exceed�hal which is provided by a twenty ampere circuit more ihan 30 minutes aRer lhe area has been vacated.
<br /> loaded lo no�more than eigh�y percent.A master contiol may 1513.6.2 Autometic Time SwRches: Automatic timo switches
<br /> bo ins�alled provided the individual switchos r�lain their shall have a minimum 7 day clock and be capab�e of being sot
<br /> capabili�y to tunction independently. �ircuil broakers may not for 7 diflerent day types per week and incorporale an au�omatic
<br /> be used as Uie sole means of switching. holiday"shut-o1f'tealure,which lums otf all loads for al laast
<br /> 24 hours and then resumes normally scheduled operations.
<br /> EXCEPTIONS: Automatic time switches shall also have program back•up
<br /> 1. Industnal or maw�acNring procoss areas,as capabili�ies,which provent the loss of program and time
<br /> may be requimd br produclion. sepinc�s lor a�leasl 10 hours,it power is inlerrupted.
<br /> 2. Areas less than tive porcent o�lootpnnt lor
<br /> foo�pnnts over 100,000 squam fect. Au�omatic time switchas shall incorpo2�o an over-ride
<br /> 1613.3 Daylight Zone Control:All rlaylighted zones,as switching device which:
<br /> delined in Chapter 2,both under overhead glazing and a) is readily accossiNe;
<br /> adjacen�to vertical glazing,shall be provided wilh individual b) is localed so�hat a person using tho device can see�he
<br /> contro�s,or dayligh4or occupant-sensing au�omalic conYols, Iic�hts or ibe aroas coNroiled by�he swi�ch,or so that ihe
<br /> which control the lights indepcndenl ol general area lightinc�. aroa being illuminated is annunciated;and
<br /> c) is manually operated;
<br /> Contic�uous daylighl zones aAjacont to vertical c�lazing are �) allows iho lighling to remain on for no more ihan two hours
<br /> allowed to bo conirolled by a single coNrolling dovice providod �yryen an over•ride is initiated;and
<br /> ihat ihey do nol includo zones facing more ihan lwo adjaceN e) con�rols an area nol axceeding S,OOG square leet or 5
<br /> cardinal orieNations(i.e. norih,east,soolh,wesQ. Dayli�hl porcenl of lootprint for foo�prints over 100,000 square feat,
<br /> zones under ovenc�aa�lazin�moro Ihan 151eet trom Ihe whichever is c�reater.
<br /> porimeter shall be con;rolled separrtcly Irom dayligh�zones
<br /> adjacen�to vehical glazing. 15137 Commissioning Requlrements:For lighting controls
<br /> EXCEPTION: which include daylic�ht or occupanl sensing au�omatic con�rols,
<br /> Daylic�ht s�uces enciosed by walls or ceilin� aulomatic shutol(controls,ocwpancy sensors,or automatic
<br /> height partilions and containing 2 or fower light limo switches,the lighling contmis shall be tested�o ensure
<br /> fixtures are not required lo have a separate switch for �ha�conirol devices,components,equipment and systems are
<br /> ca,ibm�ed,adjusted and operete in accordance wi�h approved
<br /> geneml ama lighting. plans and specilicalions. Sequences ol opem�ion shall be
<br /> 1513.4 Displey, Exhibitlon,end Specialty Llghting (unclionally tested to onsure they oper.�to in accordance with
<br /> Conlrols:NI display,exhibilion,or specially ligh�ing shall bo approved plans and specilica6ons. A complete repod o�test
<br /> cor Irolled independently ol�eneral area li�hting. procedu�es and msul�s shall be prepared and liled wi�h tho I
<br /> owner. Drawin�notes shall require commissioning in i
<br /> accordancc wilh this paragraph. ��