<br /> 1001 WUNnpp1 SbN NoneWMktl Fne%CoOs ConW Wb F>IM IYNM0.4M 2007-IfJM
<br /> Lightlng -General Requirements 761�.6 Automatk Shut-0It Controls,�rior:�ro�or
<br /> 761�Lightlny Controls. Lighting,induding exempt li3hting in �ipMing not intended Por 24-hour oon8nuous use ehall be
<br /> SeN:�n 1512,shall comply with this section.Where occupancy automatlaly awit�hed by timer,photocell,cr a combinatlon of
<br /> sensors are cited,thay shall have the features listed in Section timer and photocell.Aulomatic time switches must also bave
<br /> 1513.6.1.Where automatic time switches are cked,they shall Frogrem badc-up capabilities,which provent tl�e bss of ,
<br /> have the features listed in Sedion 1513.6.2. Pro9rem and time settings for at least 10 hows,ff power is .
<br /> inlerrupted. ,
<br /> 157�.1 Loeal Control and Acc�wibitily:Each space, 1613.8 Automatic 4but-0ff Controls,Int�dor:Olfice '
<br /> enGosed by walls or ceiling-height partRions,shall be provided buildings greater than 5,C00 sq.1L and all acheol Gaasrooma I
<br /> with lighting controls lowted within that space.The lighting ahall be equipped with sepante automatic controls to shut oB �
<br /> controls,whether one or more,shatl be capable of luming ofl the lightinfl during unoccupied hours.Autumatic controla may '��
<br /> all lights within the space.The controls shall be readily pe an occupanq senaor,time swi!ch,or clher devica capabb ��
<br /> accessible,at the point of entry/exit,to personnel occupying or of automatica!ly shutting oB lightlng.
<br /> using the space.
<br /> El(CEPTIONS:The foliowing lighting controls may be EXCEPTIONS:
<br /> 1. Areas that musl be continuc usly illuminated,or
<br /> centrelized in ramote locations: illuminated in a manner requiring manual
<br /> 1. Lighting controls for spaces which must be used
<br /> as a whole. operation at tha lighting.
<br /> 2. AutomaGc controls. 2. Emergenq lighting syalems.
<br /> 3. Switching for indushial or m¢nutacturing process
<br /> 3. Confrols requiring lrained operetors. facilities as may be required for produdion.
<br /> 4. Controls tor safery hazards and security.
<br /> 1b13.2 Area Contrels:The maximum IigMing po�ver tiiat may �613.6.1 Occupancy Sensors:Gaupancy sensors shall be
<br /> be controlled from a single switch or automatic conUol shall not �Pable ot aWomatically tuming off all the lighb in an area, no
<br /> exceed that which is provided by a N✓enty ampere cirait more than 30 minutes aRer the area haa been vacated.
<br /> loaded to not more than eighty percent.A master control may 161�.6.2 Automadc Time Switohs:Automalic Ume switches
<br /> be installed provided the individual switches retain their shall have a minimum 7 dey Godc and be capable of being set
<br /> capability to fundion independently.Circuit breakers may not for 7 diHerent day ypes per week and incorporate an automatic
<br /> be used as the sole means of switching. holiday"shutoH'feature,which tums oH all loads(or at least
<br /> EXCEPTIONS: 24 hours and then resumes nortnally scheduled operations.
<br /> 1. Industrial or manufaduring process areas,as Automatic time switches shall also have program back-up
<br /> may be required for produdion. capabilities,which prevent the lou of program and tima
<br /> 2. Area�less than five percent of footprint for setlings for at least 10 hours, if power is intertupted.
<br /> footprints over 100,000 square feet. Automatic time switches shall incoryorete an over-ride
<br /> 1513.1 Daylight 2one Control:All daylighted zones,as ��tching device which:
<br /> defined in Chapter 2,both under overhead glazing and a) is readily accessible;
<br /> adjacent to vertical glazing,shall be provided with individual b) is located so that a person using the device cFin see lhe
<br /> controls,or daylight�or occupant-sensing automatic controis, lights or the areas controlled by the switch,or so that the
<br /> which control the lights independent of genenl area lighting. area being illuminated is annunciated;and
<br /> Contiguous daylight zones adjacent to vertical glazing are c) is manually operated;
<br /> allowed to be controlled by a single controlling device provided d) allows the lighting to remain on for no more than two hours
<br /> that they do not indude zones facing more than hvo adjacent �en an over-ride Is iniliated;and
<br /> cardinal orienlations(i.e. north,east,south,west).Daylight e) controls an area not exceeding 5,000 aquare feet or 5
<br /> zones under overhead glazing more than 15 feet from the percent of footprint for footprints over 100,000 squaro feet,
<br /> perimeter shall be conlrolled separately from daylight zones ��chever is greater.
<br /> adjacent to vertical ylazing. 1513.7 Commissioning Rsquirem�nb:For IighGng conVols
<br /> EXCEPTION: which indude daylight or occupant sensing automatic conlrols,
<br /> Daylight spaces endosed by wails or ceiling automatic shut-oH controls,occupanq sensors,or automatic
<br /> height partitions and containing 2 or fewer light lime switches,the lighting controls shall be tested to ansure
<br /> fixtures are not required to have a separate switch for that conhol devices,components,equipment and systems are
<br /> general area lighting. calibrated,adjusted and operate in accordance with approved
<br /> plans and specifications.Sequences of operation shall be
<br /> 1513.4 Display,Exhibition,and Speclalty Lighting fundionally tested to ensure they operate in accordance with
<br /> Conhols:All display,exhibition,or specialty lighting shall be approved plans and specifications.A compbte report of test
<br /> conlrolled independently of general area lighting. procedures and results shall be prepared and filed with the
<br /> owner. Drawing notas shall require commissioning in
<br /> accordance with this paragraph.