2001 Washin ton State Nonresidential Ener Code Compliance Form
<br /> . . . �
<br /> 2001 WasM1ingbnSG�eNonresqenlalEnergyGo4eComplicnceFartns Hm�seE��ro�0�7-NJM
<br /> Lighting -General Requirements 1513.5 Automatfc Shut-0H Controls,�er�or:�erior
<br /> 15?3 Li htin Controls. Li htin lighting not intended for 24-hour continuous use shall be
<br /> g g g g,including exempt lighting in automatically switched by timer,photocell,or a combination of
<br /> Section 1512,shall comply with this section.Where occupancy timer and photocell.Automatic time switches must also have
<br /> sensors are ciled,they shall have the features listed in Sectian program back-up capabilities,which prevent the loss of
<br /> 1513.6.1.Where automatic time switches are cited,ihey shall program and time settings for at least 10 hours,if power is
<br /> have the(eatures listed in Section tF13.6.2. intern�pted.
<br /> 1573.1 Lowl Control and Accessibility: Each space, 1513.6 Automatic Shut-Off Controls,Interior:Office
<br /> enclosed by walls or ceiling•height partitions,shall be provided buildings greater than 5,000 sq.ft.and all school classrooms
<br /> with lighting controls located within ihat space.The lighting shall be equipped wlth separate automatic controls to shut off
<br /> conimis,whether one or more,shall 6e capable of turning off the lighling during unoccupied hours.Automatic contrals may
<br /> all lighls within the space.The controls shall be readily be an occupancy sensor,time switch,or otherdevice capable
<br /> accessible,at the poin�of entry/exit,to personnel occupying or of automatically shutting off lighling.
<br /> using the space.
<br /> EXCEPTIONS:The following lighting controls may be �CEPTIONS:
<br /> t. Areas that must be continuously iiluminated,or
<br /> centralized in remote locations: illuminated in a manner requiring manuai
<br /> 1. Lighting controls for spaces which must be used operation of Ihe lighdng.
<br /> as a whole. 2. Emergency lighting systems.
<br /> 2. Automatic controls. 3. Switching for industrial or manufacturing process
<br /> 3. Controls requinng trained operators. facilities as may be required for produclien.
<br /> 4. Controls for safety hazards and security.
<br /> 1513.6.1 Occupaney Sensors:Occupancy sensors shall ba
<br /> 1513.2 Area Controls:The maximum lighting power that may capable of automatically tuming ott all the IighLs in an area,no
<br /> be controlled trom a single switr.h or autematic control shall not more than 30 minutes aRer the area has been vacated.
<br /> ezceed that which is provided by a hventy ampere circuit �513.6.2 Automatic Time Switches:Automatic lime swilches
<br /> Icaded to not more than eighty percent.A master control may
<br /> be installed provided lhe indiviJual sw�tches relain their shall have a minimum 7 day clock and be capable of being set
<br /> capabiliry to funr,tion independenfly.Circuil breakers may�ot �or 7 diflerent day types per week and incorpo2te an automati:
<br /> be used as ihe sole means of switching. holiday"shut-off"feature,which turns o(f all loads for at least
<br /> EXCEPTIONS: 24 hours and then resumes nortnally scheduled operations.
<br /> Automatic time switches shall also have program back-up
<br /> 1. Induslrial or manufacturing process areas,as capabilities,which prevent the loss of program and time
<br /> may be required for producticn. settings for al least 10 hours.if power is inlerrupted.
<br /> 2. Areas less than five percent of footprint for
<br /> footprinis over 100,000 square feel. Automatic time switches shall incorporate an over-ride
<br /> 1513.3 Daylight Zone Control:All tlaylighted zones,as switching device which:
<br /> defined in Chapler 2, both under overhead glazing and a) is readily accessible;
<br /> adjacent to vertical c�lazing, shall be provided with individual b) is located so that a person using the devir.e can see the
<br /> wntrols,or daylighl-or occupant-sensing automatic conirols, lights or�he areas conlrolled by the switch,or so that the
<br /> which conlrol lhe lights independent of general area lighting. area 6eing illuminated is annunciated;and
<br /> Contigu�us daylighl zones adjacent to vertical ylazing are c) is manually operated;
<br /> allowed to br.controlled by 2 single controlling device provided d) allows the lighting to remain on for no more Ihan hvo hours
<br /> when an over•ride is initiated;and
<br /> that ihey do not include zones(acing more ihan hvo adjacent e) wntrols an area not exceeding 5,000 square feet or 5
<br /> cardinal orientations(i.e.north,east,,outh,west).Daylight percent of footpnnt for footprints over 100.000 square feet,
<br /> zones under overhead glazing more than 15 feet frcm the ,vhichever is greater.
<br /> perimeter shtdl be controlled separately from daylight zones
<br /> adjacent lo vertical glazing. 15137 Commissioning Requirements: For lighting controls
<br /> EXCEPTION: which include daylight or occupant sensing automatic controls,
<br /> Daylight spaces enclosed by walls or ceiling automatic shut-off contmis,occupancy sensors, or auromatic
<br /> height partitions and containing 2 or fewer light time switches,the lighting wntrols shall be tested to ensure
<br /> fixtur=.s are not required to have a separate switch for that control devices,components,equipment and systems are
<br /> general area lighting. calibrated,adjusted and operete in accordance with approved
<br /> plans and specifications.Sequences of operatlon shall be
<br /> 1513.4 Display, Exhibition,and Specialty Lighting functionally tested to ensure ihey operate in accordance with
<br /> Controls:All display, exhibition,or specialty lighling shall be approved plans and specifications.A complete report of test
<br /> controlled independanUy of general area liyhtiny. procedures and results snall be prepared and filed with the
<br /> owner. Drawina noles shall require commissioning in
<br /> accordance with this paragraph.