Laserfiche WebLink
F oge Y 1 <br />AM FIRE DEPARTMENT• <br />FIRE PREVENTION BUREAU t 4, R t <br />h ;ram 'PLAN REVIEW SECTION ' <br />TO: DAVE TYLER <br />FROMs SAN PRESTON <br />DATE: 1-24-92 <br />SEPA 42-92 <br />EFD PC 092-610, VARIANCE #1-92 <br />16417 19TH AVE SE <br />ALFY'S PI22A <br />NEW 6888 SO FT RESTAURANT <br />1. FIRE FLOW — <br />BASED UPON 6,288 SO FT OF TYPE V—N, SPRINKLERED; <br />CONSTRUCTION THE FIRE FLOW REQUIREMENT IS THE UNIFORM <br />FIRE CODE MINIMUM OF 1,599 GPM. <br />2. ACCESS — <br />OK AS SHOWN ON THE SITE PLAN REVIEWED. <br />3. HYDRANTS — <br />EXISTING HYDRANT LOCATIONS ARE OK.' <br />4. SPRINKLER SYSTEM — <br />CITY ORDINANCE #1759-94 REQUIRES THAT ALL OCCUPANCIES <br />OVER 6.809 SO FT BE PROVIDED AN AUTOMATIC FIRE <br />SUPPRESSION SYSTEM. A SPRINKLER SYSTEM INSTALLED IN <br />ACCORDANCE WITH UNIFORM BUILDING CODE STANDARD 38-1 OR <br />NFPA STANDARD 13 IS ACCEPTABLE. <br />S. FIRE ALARM SYSTEM — <br />WHERE THE ASSIGNED OCCUPANT LOAD EXCEEDS 300. A MANUAL OR <br />AUTOMATIC FIRE ALARM SYSTEM INSTALLED IN ACCORDANCE WITH <br />UNIFORM FIRE CODE STANDARD 14-1 IS REQUIRED. <br />6. PORTABLE FIRE PROTECTION — <br />A PORTABLE FIRE EXTINGUISHER WITH A MINIMUM UL RATING OF <br />2A MUST PROVIDED WITHIN 75' TRAVEL DISTANCE, ON EACH <br />FLOOR, OF ALL PORTIONS OF EACH BUILDING DURING <br />CONSTRUCTION. <br />PORTABLE FIRE PROTECTION MUST BE PROVIDED THROUGHOUT THE <br />BUILDING AS REQUIRED BY ARTICLE 10 OF THE UNIFORM FIRE <br />CODE PRIOR TO ISSUANCE OF ANY CERTIFICATE OF OCCUPANCY. <br />7. PREMISES IO — <br />THE CORRECT ADDRESS MUST BE POSTED AT THE STREET ENTRY OR <br />ON THE BUILDING NEAR THE MAIN ENTRY IN MANNER THAT IS <br />CLEARLY LEGIBLE AND VISIBLE FROM THE STREET. <br />B. ALL REQUIRED ACCESS ROADS AND FIRE HYDRANTS MUST BE IN <br />SERVICE PRIOR TO COMMENCEMENT OF CONSTRUCTION. <br />