Gary McCormick <br />Plan Check No. 57283 <br />December 9, 1997 <br />Page 2 of 2 <br />8. Provide detail of attic ventilation type, size, and location. Show the required net area calculations <br />assuming approximately 75% of the vent area is net area unless the actual net area is given from <br />the manufacturer. The required ventilation area ratio is 1/150 of the attic area or 1/300 of attic <br />area if at least half of the vent area is more than 3' above eave vents (providing the remaining <br />portion of the vent area). Opening to have 1/4" 4 6.4mm) corrosion, resistant metal mesh <br />covering. (1505.3) Vented blocking shall not compromise the structural integrity of shear <br />transfer, roof diaphragm to shear wall. <br />9. Show under floor ventilation opening size and locations equal to 1 sq. ft. for each 150 sq. ft. <br />(0.076m' for each lOm') of under floor area. Openings shall be as close to corners as practicable <br />and shall provide cross ventilation along the length of at least two opposite sides. Openings shall <br />have 1/4" (6.4mm) corrosion resistant metal mesh covering. Show the required net area <br />calculation assuming approximately 75% of the vent area is net area unless the actual net area is <br />given from the manufacturer. (2317.7) <br />Prepare a response letter showing where each item in this correction letter is addressed on the plan set. <br />Upon resubmittal of the drawings, your application will be given priority and plan review will <br />commence. <br />All required submittals shall be of sufficient detail and contain sufficient information to ensure that the <br />proposed structure will be cor;ructed in compliance with all adopted codes. <br />Sincerely, <br />AW <br />Jeff Heilman <br />Development Technician <br />tHjdtdedia.duc(7-8) <br />