<br /> Lighting - General Requirements '1513.6 Automatic Shut-ON Controis, Interior: Buildings
<br /> 1513 Li hting Controls. Li htin g exempt lighting 9reaterthon 5,000 sq. ft. and all school classrooms shall ba
<br /> fl g g, includin equipped with sep�rate outom�lic controls to shutaHthe
<br /> in Section 15'12, shall comply with this section. Whero lighting during unoccupied hours. Within these buildings, all
<br /> occuponcy sensors are cimd, Ihey sholl have the fe�tures office are�s Iess Ihan 300 ft'onclosed 6y wolls or ceiling-
<br /> lisied in Section 1513.6.1. Where outomotic time switches are height parti[ions, and oll meeting and con(erence rooms, and
<br /> crted,they sh�ll h�ve the features listed in Section '1513.6.2. all school dassrooms, sh�ll be equipped with occupancy
<br /> '1513.1 Loeal Control and Accessibility: Each space, sensors that comply Section '1513.6.'I. For other sp�ces.
<br /> enclosed by walls or ceiling-heighl partitions, sholl be provided automatic controls moy be an occupancy sensor, time sv+itch,
<br /> with IigMing controls located wiihin that spoce. The lighting or othur device capable uf automatically shutting oH lighting.
<br /> controls, whether one or more, sh�ll be cupoble of turning off EXCEPTIONS:
<br /> all lights within the spaca The controls shall be readily �. Amas thot mwt be continuously iliuminated(e.g.,
<br /> ❑ccessibte, nt the point of entry/exit, to personnel occupying or 24-hour convenience siores), ar illuminoted in a
<br /> usino thc space, mannef requiring monu�l operation of the
<br /> EXCEPTIONS:�ihc following lighting controls m�y be lighting.
<br /> centrolized in remote locations: 2. Emergency lightin9 systems.
<br />� 'I. Lighting controls for spaces which must be used 3. Sv+i[chiny for industrial ar manufacturing process
<br /> os a whole. ��cilities as may 6e required for production.
<br /> 2 Automotic controls. 4. Hospit�ls and laborotory spaces
<br /> 3. Controls rcyuiring troined opemtors.
<br /> 4, Controls far safety h�zards �nd sewriry. 5. .4reas in which medicol or dent�l tasks are
<br /> performed are exemp[from the occupancy
<br /> 15'13.2 Area Controls:The maximum lighting pawcr that may sensor requircment.
<br /> be controlled from a single switch or au[omatic<ontrol shall not �5'13.6.'I Oecupanry Sensors:Occupancy sensors shall be
<br /> exceed th�t which is provided by a twenty ampere circuit
<br /> looded[o not more than eighty percent. A moster control m�y ��P�61e of automaticaily turning oH all the lights in on area, no
<br /> be instolled provided the individuol switches retain their more th�n 30 minutes�fter the area has 6een vocated. Light
<br /> c�pobility to function independently. Circuit bre�kers may not fxt�res contwlled by occupancy sensors shall hnve a v+ail-
<br /> be used as the sale means o(switching. rr�ounted, rr��nual svntch copable o'turning off lights when tr,.�
<br /> EXC[PTIONS: spnce is occupicd.
<br /> 1. Industriol or m�nu`acturing process�reas, as 15'13.6.2 Automatic Time Switches:Automatic timo swrtch�. :.
<br /> may 6e required for production. shall have o minimum 7 day dock and be c.;p�ble o(being src
<br /> 2. Are,s less than fve peroent of footprint for (or 7 diHerent day types per week and incorporato an
<br /> tootprints over 100,000 squ�re feet. �utomatic holidoy"shuFoff'(eature, which tums off all loads for
<br /> ot leas[24 hours and[hen resumes normally schedWed
<br /> 75'13.3 Daylipht Zone Control:All doylighted zones, as opemticns. Automotic time sv+itches shall aL•o have progrom
<br /> tlefned in Chapter 2, L-oth under overhead gl�zing and y�ck-up capabilities,vihich prevent ihe loss of program and
<br /> adjacent to vertiwl glazing, sholl 6e provided with individu�l �ime settings for at Icost �0 hours, if power is interrupted.
<br /> controls, or d�ylight-or occupant-sensing automotic controls, Automatic time sv.•itches shall incorporote an over-ride
<br /> which control the liyhts independent of gener�l area lighting. switchiny device which:
<br /> Contiguous doyliyht zanes adjocent to vertical gtazing am �) is readily accessible;
<br /> allowed ta be cantrolled by a single ccntrolling devico provided b) is located so Ihot o person using the device c�n see the
<br /> th�t they do not include zones facing mom than hvo �djocent lights or the areos controlled by the switch, or so that the
<br /> wrdinal orientotions(i.e, north, cast, south, west). D�ylight arca heing ilWmin�ted is annunciated; and
<br /> zones under overhead glozing more than 15 fect from the c) is monu�lly operated:
<br /> perimeler shall be controlled separatcly from daylight zones
<br /> ❑djacent to vertical glazing. d) allows the lighting to remoin on (or no moro th�n two hours
<br /> when an over-ride is initiated�, and
<br /> EXCEPTION: e) controls on�rea not exc_eding 5,000 square feet or 5
<br /> Daylight spaces endosed by w�lis or ceiling percent of foatprint for footprints over 100,000 squore feet,
<br /> heiyht partitions ond containing 2 or fewer light whichever is greater.
<br /> fxtures ore not required to h�ve a seporate switch for
<br /> gener�l arca ligliting. '1573.7 Commissioninp Requirements: For lighting controls
<br /> 'IS'13.4 Display,Exhihition,and Specialty Liphting which include d�ylight or occupant sensing autom�tic controls,
<br /> outomatic shut-off controls, occupancy sensors, or automatic
<br /> Controls: All disploy, exhibition, ar specialry lighting shall be time switches, the lighting controls shall 6e te�ted to ensure
<br /> controlled independently of guneral ore� lighting. that control devices, components, equipmen:�nd systems ore
<br /> '15'13.5 Automatie ShubOH Controls, Exterior. E��.rior colibr�ted, adjusted and opera[o in acwrdance with approvcd
<br /> lighting not intended for?4-hour continuous use shall be plans and specifications. Sequcnces of operation shall be
<br /> automotically switched by timer, photocull, or o combin�tian of function�lty tested to ensum they operate in xcordance with
<br /> timer and photocell. Automotic time switches must also have approved plans and specifwtions. A complete repart of test
<br /> pragram back-up capabilities,which preven[lhe lass�f procedures and results shall he prepared �nd fiied with the
<br /> progrnm and time settings for at Ieast 10 haurs, if powcr is owner. Drowing notes shatl require commissioning in
<br /> intartupted. ❑cmrdonce with this por�groph.