Structural Desi6n Associates <br />North Star Building <br />2210 Hewitt Ave., Suite 201 <br />Everett, WA. 98201 <br />(425)339-0293 <br />May 31, 2000 <br />Lakeland Fiomes, Inc. <br />Altn: Steve Warbis <br />PO Box 3205 <br />Everett, WA 98206 <br />Subject: Foundation Wnll at 1928 112'�' St. SW - Everett, WA <br />To whom this may concem: <br />At the rcquest of Steve Warbus, this ofTicc reviewed the faundation wall locnted et thc <br />subject residence for equal backfill, full height, on both sides.. <br />The 8 inch thick x 10 foot liigh concrete wall must be reinforced with # 4 at 18 inches on <br />center each way. The backfill soil must be placed in I-foot loose lifts equally on cach <br />side of the wall. Soil compection should meet or exceed 95% rnodified proctor at <br />optimum moisture content. <br />Please contact t�s o�ce if you hnve any questions conceming this plan chnnge. <br />Chris Covinet'�n�P.l�. <br />I EXPiRES � - � - 0 Z_ <br />