� <br />Plan Check No: 39477 thru 39500 <br />April 26, 1993 <br />Page Three of Four <br />+ 19. A clear space 30 inches wide, 29 inches high and l7 inch :s in depth shall be provided under <br />each lavatory. Secdon 3106(k)7c. A cicar �oor sp�ce nut icss than 30 inches wide and ,18 <br />inches deep is required in front of lavau�rics and sin�cs. S.ction 3106(k)7a. <br />� 20. The bottom of at least one mirro� shall be within 40 inche s of the floor. Secdon 3105(b}3 and <br />3106(k)8. <br />✓ 21. Hand drying equipment and toilet accessories shall be placed within 40 inches of the floor. <br />Section 3106(k)8. <br />���22. The shower stalls must be accessible per Section 3106(k)10. <br />�/ 23. Thc urinal must comply with Section 310G(k)6. <br />� 24. The first floor smoke detectors in Units C& D should be located away from the vaulted <br />ceiling area. <br />� 25. Provide protecUon for water heater and Cumace in units C& D per U.M.C. Section 508. <br />� 26. Please provide energy calculations and insulation details for the Rec Building. <br />v 27. Please provide the following structural calculations: <br />I'YiI� ���� 20 <br />`! t' i-+`� <br />p �.,r2y �'ae <br />R�'F�1 C�lN�?' <br />A) Lateral design calculations Cor Units E Rc F <br />B) Framing calculations for the Rec Building <br />No alternate pile details or calculations were provided for Units A, D, E, F or the Rec <br />Building. <br />The soils report indicates this type of foundation may be desirable for some of these building <br />types. Please clarify. <br />