Laserfiche WebLink
CONTOUR WOUSTRIES <br />7 November 199G <br />City of Everett <br />inspection Department <br />3200 Cedar St. <br />Everett, WA 98201 <br />Attention: Tim Alaniz <br />Reference: Our letter Jated 23 October 1996 <br />Dear Tim, <br />0 0u H NOV 131996 <br />11111 <br />CITY OF EVERE17 <br />Bldg. Permit Counter <br />Thank you for your timely consideration of our proposed deletion A ground fault <br />circuitry from a 6000 �-.mp switchboard at 1415 75th Street SW, Everett, WA. We have <br />reviewed the requirements with Mr. Lorne Wallitner of Rodgers Electric Company, and <br />understand the equip rent protection purpose of ground fault circuitry in our electrical <br />service. <br />We have reviewed the requirements specifically in regard to the three main fused <br />bolted pressure switches and have found that GFI protection should be provided for the <br />1,600 and 2,000 ar, ,) switches since the equipment connected to those feeders will not <br />provide an immediate health or injury hazard shculd power become unexpectedly <br />disconnected in the event of a ground fault. <br />Our main safety concern is the loads served by the 2,500 amp switch. The possibility of <br />injury from a power outagq on loads served by that section is significant enough that the <br />potential equipment damage is less important than the personnel hazard an outage <br />could produce. Therefore, with your department's approval, it is our plan to proceed <br />with ground fault protection eliminated from only distribution Section "A", fed from the <br />2,500 amp bolted pressure switch. <br />We trust that you will find the foregoing acceptable and we thank you for your <br />consideration and cooperation. <br />Sincerely Yours <br />el Convis <br />Engineering Manager <br />2916 100th St. S.W., Unit A, Everett, WA 96204.1474 a (206) 355-0616 9 Fax: (206) 355.7360 <br />