Laserfiche WebLink
A <br />VOL IC WORKS <br />ENGINEERING / PUBLIC SERVICES DEPARTMENT <br />April 3, 2003 <br />Mr. Kevin McLean <br />WA Botting Co. <br />19405-144 Avenue NE <br />Woodinville, WA 98072 <br />RE: Owner: <br />Job Address: <br />Plan Check No: <br />Dear Mr. McLean: <br />Agilent <br />1615 — 75'h Street SW <br />M303-034 <br />In response to your application for a mechanical permit, your plans have been examined and you are <br />advised that the issuance of a permit is being withheld for the reasons listed below <br />The plans indicate the attic spaces being utilized as plenums for the return air. Since these <br />spaces are full of exposed wood framing and PVC. UMC 601.4 would appear to require the <br />return air to travel through ductwork. <br />Upon rcsubmittal of the drawings, your application will be given priority and plan review will <br />recommence. <br />All required submittals shall be of sufficient detail and contain sufficient information to ensure that <br />the proposed structure will be constructed in compliance with all adopted codes. <br />Sincerely, <br />m� <br />J <br />Steve Miller <br />Associate Engineer <br />DEDLTL`1 "Sn NH1"W1USdH 1161$45S STSMI <br />CITY OF EVERETT• 3200 Cedar Street • Everett, WA 98201 • (425) 257.8200 • Fax (425) 257-8856 <br />